| 2011-01-11 13:53:43 | 1919 NORTH FLAGLER DRIVE, 2ND FLOOR | | | PERMIT #11010081 | | | MASTER #10070710 | | | REVIEW COMMENTS - FIRE | | | | | | | | | CONFERENCE ROOM LOCATED TO THE WEST HAS TWO SPRINKLERS | | | LOCATED IN THE 8-6 CEILING. THE SPRINKLER SPRAY WILL BE | | | OBSTRUCTED BY THE 8-2 CEILING/SOFFIT. | | | | | | THE CORRIDOR SPRINKLER ADJACENT TO THE WOMEN'S RESTROOM | | | IS LOCATED MORE THAN 7-6 FROM THE WALL. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|