| Plan Review Notes For Permit 11010070 |
| Permit Number |
11010070 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-13 10:01:20 | FBC PLUMBING 2007 | | | NFPA 99C 2002 | | | REVISION REVIEW #1 | | | DENIED: | | | | | | 1. PLEASE SUBMIT VACUUM PUMP MANUFACTURERS | | | SPECIFICATIONS SHOWING THAT 3/4" MAIN AND 1/2" RISERS | | | ARE SUGGESTED OR REQUIRED. RAMVAC VACUUM PUMPS REQUIRE | | | 2" MAINS BELOW FLOOR SLOPED AT 1/4" PER FOOT. VACSTAR'S | | | SMALLEST PUMP VS 20 REQUIRES A MINIMUM OF 1" MAIN - | | | ETC. | | | | | | 2. SANITARY DRAWINGS APPEAR TO BE ELIMINATING THE | | | DRAINS FOR THE CHAIRS IN TREATMENT ROOMS 1 & 3. ARE | | | THESE CHAIRS EXISTING? | | | | | | 3. NFPA 99C 2002 5.3.3.6.3 VACUUM DRAINS ARE TO BE | | | DIRECTLY CONNECTED TO THE SANITARY, TRAPPED, AND | | | VENTED. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | |
|