2011-01-20 10:52:41FBC 2007 PLUMBING PLAN REVIEW #1
 DENIED:
  
 1. ROOM #1-119 - THE TOILET STALL DOES NOT COMPLY WITH
 11-4.17 FIGURE 30E.
  
 2. TOILET ROOMS #1-116, #1-117, #1-118 DO NOT COMPLY
 WITH 11-4.1.3(11) TOILET FACILITIES. IF TOILET ROOMS
 ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET
 ROOM SHALL COMPLY WITH SECTION 11-4.22
  
 3. NO DRINKING FOUNTAIN WAS FOUND ON PLAN. FBC PLUMBING
 2007 403.1 REQUIRED FIXTURES 1 PER 100 OCCUPANTS
 REQUIRED.
  
 4. PLUMBING 911 CIRCUIT VENTING 911.2 VENT CONNECTION.
 THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN
 THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL
 CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED
 IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE
 SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE.
  
 REVIEW BY LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 (561) 805-6692
 FAX (561) 653-2692