| Plan Review Notes For Permit 11010034 |
| Permit Number |
11010034 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-20 10:52:41 | FBC 2007 PLUMBING PLAN REVIEW #1 | | | DENIED: | | | | | | 1. ROOM #1-119 - THE TOILET STALL DOES NOT COMPLY WITH | | | 11-4.17 FIGURE 30E. | | | | | | 2. TOILET ROOMS #1-116, #1-117, #1-118 DO NOT COMPLY | | | WITH 11-4.1.3(11) TOILET FACILITIES. IF TOILET ROOMS | | | ARE PROVIDED, THEN EACH PUBLIC AND COMMON USE TOILET | | | ROOM SHALL COMPLY WITH SECTION 11-4.22 | | | | | | 3. NO DRINKING FOUNTAIN WAS FOUND ON PLAN. FBC PLUMBING | | | 2007 403.1 REQUIRED FIXTURES 1 PER 100 OCCUPANTS | | | REQUIRED. | | | | | | 4. PLUMBING 911 CIRCUIT VENTING 911.2 VENT CONNECTION. | | | THE CIRCUIT VENT CONNECTION SHALL BE LOCATED BETWEEN | | | THE TWO MOST UPSTREAM FIXTURE DRAINS. THE VENT SHALL | | | CONNECT TO THE HORIZONTAL BRANCH AND SHALL BE INSTALLED | | | IN ACCORDANCE WITH SECTION 905. THE CIRCUIT VENT PIPE | | | SHALL NOT RECEIVE THE DISCHARGE OF ANY SOIL OR WASTE. | | | | | | REVIEW BY LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | (561) 805-6692 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] | | | | | | | | | |
|