2011-01-05 12:24:27222 PICADILLY STREET
 PERMIT #11010034
 REVIEW COMMENTS - FIRE
  
  
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION (NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS).
  
 CORRIDORS SHALL PROVIDE EXIT ACCESS WITHOUT PASSING
 THROUGH INTERVENING ROOM TO REACH AN EXIT (REFERENCE:
 SECTION 7.5.1.2 OF FLORIDA FIRE PREVENTION CODE ???
 NFPA 101). THE PLANS SHOW THREE SEPARATE EXITS THAT
 REQUIRE AN OCCUPANT TO TRAVEL THROUGH AN OFFICE SPACE
 TO REACH AN EXIT. ELIMINATING THE EXIT IN OFFICE ROOM
 1-104 CREATES A DEAD-END CORRIDOR IN EXCESS OF 20 FEET
 IN LENGTH.
  
 SHEET A1.0 REFERENCES A SEPARATE PERMIT FOR FIRE ALARM
 WORK. NO FIRE ALARM WORK APPEARS ON ANY SHEETS.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  