| Plan Review Notes For Permit 11010025 |
| Permit Number |
11010025 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-06 09:57:50 | DENIED BY MECHANICAL | | | | | | 1) THE APPROVED MECHANICAL PLANS WERE SIGNED AND SEALED | | | BY BERNARD JONES, A FLORIDA LICENSED ARCHITECT. THE | | | REVISED PLANS THAT WERE SUBMITTED HAVE THE ARCHITECT'S | | | TITLE BLOCK BUT HAVE NOT BEEN SIGNED AND SEALED BY HIM | | | AS REQUIRED BY FS 481. | | | | | | 2) PLEASE USE THE NEW REVISED FLOOR PLAN TO SHOW THE | | | LOCATIONS OF HVAC SYSTEM AND NOT THE EXISTING FLOOR | | | PLAN DEMO PLANS. | | | | | | 3) SPECIFY THE CFM AT EACH OF THE SUPPLY OUTLETS ON THE | | | DRAWINGS. | | | | | | 4) SPECIFY THE SIZES OF ALL OF THE SUPPLY AND RETURN | | | DUCTS AND GRILLS ON THE PLANS. | | | | | | 5) THE ENERGY CALCULATION FORM 1100A-08 IS REQUIRED TO | | | BE SIGNED BY THE OWNER/AGENT. | | | | | | 6) THE EQUIPMENT SIZING SUMMARY LISTS THE TOTAL | | | CALCULATED COOLING LOAD AS 19753 BTU AND THE SPECIFIED | | | EQUIPMENT HAS A TOTAL COOLING CAPACITY OF 27600 BTU. | | | SECTION N1107.AB.1.1 OF THE REVISED ENERGY CODE STATES | | | THAT THE COOLING EQUIPMENT SHALL BE SELECTED SO THAT | | | ITS TOTAL CAPACITY IS NOT LESS THAN THE CALCULATED LOAD | | | BUT NOT MORE THAN 1.15 TIMES GREATER THAN THE TOTAL | | | CALCULATED LOAD. THE SPECIFIED 2.5 TON UNIT APPEARS TO | | | BE TOO LARGE. BASED ON THE CALCULATIONS A 2 TON UNIT IS | | | REQUIRED. PLEASE CLARIFY. | | | | | | ROBERT MCDOUGAL | | | BLDG. PLAN REVIEW | | | (561)805-6714 | | | [email protected] |
|