| 2011-01-05 14:40:33 | PLANS DENIED | | | PLEASE PROVIDE A LISTING OF THE DUST COLLECTOR PER | | | SECTION 301.5.1 FBC (M) 2007 AND 510.2.2 COMBUSTIBLE | | | FIBERS. | | | PLEASE PROVIDE THE MATERIALS USED FOR THE DUCTWORK PER | | | SECTION 510.8 AND TABLE 510.8 2007 FBC (M) | | | REFER TO SECTION 511.1.1 COLLECTORS AND SEPARATORS . | | | PLEASE REFER TO NFPA 664 SECTION 5.1.1 APPROVED | | | QUALIFICATIONS . | | | PLEASE REFER TO SECTION 301.12 WIND RESISTANCE. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | | | | | |
|