| Plan Review Notes For Permit 10120674 |
| Permit Number |
10120674 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-11 11:45:57 | 1221 ANDREWS ROAD | | | PERMIT #10120674 | | | EXPIRED PERMIT #09060576 | | | REVIEW COMMENTS - FIRE | | | | | | PLANS ARE DATED 02/12/09 WITH REVISIONS DATED 12/20/10. | | | SEVERAL PLAN SHEETS APPEAR TO BE MISSING. | | | | | | NO INFORMATION GIVEN ON CURRENT BUILDING USE, EXIT | | | LOCATIONS, PORTABLE FIRE EXTINGUISHER LOCATIONS ETC. | | | | | | WOODWORKING OPERATIONS SHALL COMPLY CHAPTER 31 - FOREST | | | PRODUCTS OF THE FLORIDA FIRE PREVENTION CODE 2007 | | | EDITION (NFPA 1). | | | | | | NO SMOKING SIGNS SHALL BE POSTED IN ANY LOCATIONS | | | SUBJECT TO SAWDUST GENERATION. | | | | | | PLEASE INDICATE HOW THE DUST COLLECTION SYSTEM IS | | | INTERLOCKED WITH THE MACHINERY PRODUCING SAWDUST. | | | | | | PLEASE INDICATE (MICRONS) THE SIZE OF DUST PARTICLES | | | THAT WILL BE GENERATED. | | | | | | DRAWINGS DO NOT SHOW FLOOR PLANS, ONLY SITE PLAN TYPE | | | DRAWINGS. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|