| Plan Review Notes For Permit 10120673 |
| Permit Number |
10120673 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-03-07 09:57:46 | THE NEW PLANS DO NOT REFLECT THE ELECTRICAL CODE | | | REQUIREMENTS FOR THE LIVING SPACE. AN ELECTRICAL PERMIT | | | IS REQUIRED TO UPGRADE THE SUNROOM TO THE CODE | | | REQUIREMENTS NOTED BELOW. | | | | | | NEC 210.52 DWELLING UNIT RECEPTACLE OUTLETS. GENERAL | | | PROVISIONS. IN EVERY KITCHEN, FAMILY ROOM, DINING ROOM, | | | LIVING ROOM, PARLOR, LIBRARY, DEN, SUNROOM, BEDROOM, | | | RECREATION ROOM, OR SIMILAR ROOM OR AREA OF DWELLING | | | UNITS, RECEPTACLE OUTLETS SHALL BE INSTALLED IN | | | ACCORDANCE WITH THE GENERAL PROVISIONS SPECIFIED IN | | | 210.52(A)(1) THROUGH (A)(3). | | | | | | | | | RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG | | | THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A | | | RECEPTACLE OUTLET. NEC 210.52 (A)(2). | | | A GFCI PROTECTED OUTLET IS REQUIRED AT THE REAR | | | ELEVATION. NEC 210.8, 210.52 (E) (1) | | | ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC | | | 406.11 | | | THE OUTSIDE LIGHT MUST HAVE A WALL SWITCH. NEC 210.70 | | | (A)(1). | | | | | | ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718 | | | |
|