2011-03-07 09:57:46THE NEW PLANS DO NOT REFLECT THE ELECTRICAL CODE
 REQUIREMENTS FOR THE LIVING SPACE. AN ELECTRICAL PERMIT
 IS REQUIRED TO UPGRADE THE SUNROOM TO THE CODE
 REQUIREMENTS NOTED BELOW.
  
 NEC 210.52 DWELLING UNIT RECEPTACLE OUTLETS. GENERAL
 PROVISIONS. IN EVERY KITCHEN, FAMILY ROOM, DINING ROOM,
 LIVING ROOM, PARLOR, LIBRARY, DEN, SUNROOM, BEDROOM,
 RECREATION ROOM, OR SIMILAR ROOM OR AREA OF DWELLING
 UNITS, RECEPTACLE OUTLETS SHALL BE INSTALLED IN
 ACCORDANCE WITH THE GENERAL PROVISIONS SPECIFIED IN
 210.52(A)(1) THROUGH (A)(3).
  
  
 RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG
 THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. NEC 210.52 (A)(2).
 A GFCI PROTECTED OUTLET IS REQUIRED AT THE REAR
 ELEVATION. NEC 210.8, 210.52 (E) (1)
 ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC
 406.11
 THE OUTSIDE LIGHT MUST HAVE A WALL SWITCH. NEC 210.70
 (A)(1).
  
 ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718
  