| 2011-03-02 12:49:55 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. DESIGNER TO SPECIFY DESIGN PRESSURES, FBC R301. |
| | |
| | 2ND REVIEW, PLEASE REVISE DESIGN PRESSURES TO EXPOSURE |
| | C. |
| | |
| | 2. ADDRESSED. |
| | |
| | 3. BOND BREAK REQUIRED FBC R703.6.3. |
| | |
| | 2ND REVIEW, PLAN WAS REVISED TO SHOW STUCCO OVER PAPER |
| | BACK LATH BUT BOND BREAK NOT SPECIFIED, PLEASE REVISE. |
| | |
| | 4. SHOW GRADE IN RELATION TO BOTTOM OF STUCCO AND |
| | FINISHED FLOOR, R704.1. |
| | |
| | 5" IS SHOWN, 6" REQUIRED. AS I WAS UNABLE TO LOCATE A |
| | PERMIT TO ENCLOSE THIS PORCH, PLEASE ADDRESS. |
| | |
| | 5. PROVIDE ROOM DESIGNATIONS FOR THE ROOMS ADJACENT TO |
| | THE SUNROOM. IF BEDROOMS ARE AFFECTED, SHOW EMERGENCY |
| | MEANS OF ESCAPE, FBC EXISTING BUILDING 705. |
| | |
| | AN ADJACENT BEDROOM IS SHOWN. AS IT IS NOT CLEAR THAT |
| | PREVIOUS WORK WAS DONE UNDER PERMIT, PLEASE SHOW |
| | EMERGENCY MEANS OF ESCAPE. THIS CANNOT BE THROUGH THE |
| | ALUMINUM PORCH WHICH IS NOW BEING ENCLOSED WITH A WOOD |
| | FRAME WALL. |
| | |
| | 6. ADDRESSED. |
| | |
| | 7. CONTRACTOR'S DESIGN CRITERIA (EXPOSURE B) CONFLICTS |
| | WITH SITE LOCATION AND ARCHITECT'S DESIGN CRITERIA. |
| | PLEASE CORRELATE. |
| | |
| | 2ND REVIEW, THIS PROJECT IS LOCATED IN EXPOSURE C. |
| | PLEASE REVISE ARCHITECTURAL PLAN. CONTRACTOR'S WINDOW |
| | PLAN WILL BE DISCARDED AS ALL WORK IS NOW INCLUDED IN |
| | ARCHITECT'S PLAN. |
| | |
| | 8. ADDRESSED. |
| | |
| | 9. ADDRESSED. |
| | |
| | |