2011-03-02 12:49:55****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. DESIGNER TO SPECIFY DESIGN PRESSURES, FBC R301.
  
 2ND REVIEW, PLEASE REVISE DESIGN PRESSURES TO EXPOSURE
 C.
  
 2. ADDRESSED.
  
 3. BOND BREAK REQUIRED FBC R703.6.3.
  
 2ND REVIEW, PLAN WAS REVISED TO SHOW STUCCO OVER PAPER
 BACK LATH BUT BOND BREAK NOT SPECIFIED, PLEASE REVISE.
  
 4. SHOW GRADE IN RELATION TO BOTTOM OF STUCCO AND
 FINISHED FLOOR, R704.1.
  
 5" IS SHOWN, 6" REQUIRED. AS I WAS UNABLE TO LOCATE A
 PERMIT TO ENCLOSE THIS PORCH, PLEASE ADDRESS.
  
 5. PROVIDE ROOM DESIGNATIONS FOR THE ROOMS ADJACENT TO
 THE SUNROOM. IF BEDROOMS ARE AFFECTED, SHOW EMERGENCY
 MEANS OF ESCAPE, FBC EXISTING BUILDING 705.
  
 AN ADJACENT BEDROOM IS SHOWN. AS IT IS NOT CLEAR THAT
 PREVIOUS WORK WAS DONE UNDER PERMIT, PLEASE SHOW
 EMERGENCY MEANS OF ESCAPE. THIS CANNOT BE THROUGH THE
 ALUMINUM PORCH WHICH IS NOW BEING ENCLOSED WITH A WOOD
 FRAME WALL.
  
 6. ADDRESSED.
  
 7. CONTRACTOR'S DESIGN CRITERIA (EXPOSURE B) CONFLICTS
 WITH SITE LOCATION AND ARCHITECT'S DESIGN CRITERIA.
 PLEASE CORRELATE.
  
 2ND REVIEW, THIS PROJECT IS LOCATED IN EXPOSURE C.
 PLEASE REVISE ARCHITECTURAL PLAN. CONTRACTOR'S WINDOW
 PLAN WILL BE DISCARDED AS ALL WORK IS NOW INCLUDED IN
 ARCHITECT'S PLAN.
  
 8. ADDRESSED.
  
 9. ADDRESSED.
  
  