| Plan Review Notes For Permit 10120673 |
| Permit Number |
10120673 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-12 11:56:55 | THE PLANS DO NOT ACCURATELY DEFINE THE SCOPE OF WORK | | | PROPOSED AS TO HOW THE SPACE WILL BE UTILIZED. A | | | SEPARATED ELECTRICAL PERMIT MAY BE NEEDED. ADDITIONAL | | | ELECTRIC IMPROVEMENTS MAY ALSO BE NEEDED. | | | | | | AT A MINIMUM THE FOLLOWING IS REQUIRED. | | | | | | RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG | | | THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A | | | RECEPTACLE OUTLET. NEC 210.52 (A)(2). | | | A GFCI PROTECTED OUTLET IS REQUIRED AT THE REAR | | | ELEVATION. NEC 210.8, 210.52 (E) (1) | | | ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC | | | 406.11 | | | AT LEAST ONE WALL SWITCHED-CONTROLLED LIGHTING OUTLET | | | SHALL BE INSTALLED. NEC 210.70 (A)(1). | | | | | | ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718 | | | |
|