2011-01-12 11:56:55THE PLANS DO NOT ACCURATELY DEFINE THE SCOPE OF WORK
 PROPOSED AS TO HOW THE SPACE WILL BE UTILIZED. A
 SEPARATED ELECTRICAL PERMIT MAY BE NEEDED. ADDITIONAL
 ELECTRIC IMPROVEMENTS MAY ALSO BE NEEDED.
  
 AT A MINIMUM THE FOLLOWING IS REQUIRED.
  
 RECEPTACLES SHALL BE SPACED SO THAT AT NO POINT ALONG
 THE FLOOR IN ANY WALL IS MORE THAN 6 FEET FROM A
 RECEPTACLE OUTLET. NEC 210.52 (A)(2).
 A GFCI PROTECTED OUTLET IS REQUIRED AT THE REAR
 ELEVATION. NEC 210.8, 210.52 (E) (1)
 ALL NEW RECEPTACLES MUST BE TAMPER RESISTANT. NEC
 406.11
 AT LEAST ONE WALL SWITCHED-CONTROLLED LIGHTING OUTLET
 SHALL BE INSTALLED. NEC 210.70 (A)(1).
  
 ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718
  