| 2011-01-10 11:33:52 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. DESIGNER TO SPECIFY DESIGN PRESSURES, FBC R301. |
| | |
| | 2. PROVIDE MORE INFORMATION REGARDING EXISTING |
| | CONDITIONS. IS THIS CURRENTLY HABITABLE SPACE? PLAN |
| | STATES THAT "ALUMINUM WALL" WILL BE REMOVED. WHAT TYPE |
| | OF ALUMINUM WALL; IS THIS A SCREEN ENCLOSURE WITH |
| | REMOVABLE VINYL VINDOWS? APPLICATION STATES THAT THIS |
| | IS A WINDOW REPLACEMENT, BUT PLAN APPEARS TO SHOW A |
| | PORCH ENCLOSURE. IMPACT FEES (233-5025) AND ENERGY |
| | CALCS MAY BE REQUIRED. |
| | |
| | 3. BOND BREAK REQUIRED FBC R703.6.3. |
| | |
| | 4. SHOW GRADE IN RELATION TO BOTTOM OF STUCCO AND |
| | FINISHED FLOOR, R704.1. |
| | |
| | 5. PROVIDE ROOM DESIGNATIONS FOR THE ROOMS ADJACENT TO |
| | THE SUNROOM. IF BEDROOMS ARE AFFECTED, SHOW EMERGENCY |
| | MEANS OF ESCAPE, FBC EXISTING BUILDING 705. |
| | |
| | 6. PRODUCT APPRPOVALS TO BE REVIEWED BY DESIGNER OF |
| | RECORD FBC 106.3.3. |
| | |
| | 7. CONTRACTOR'S DESIGN CRITERIA (EXPOSURE B) CONFLICTS |
| | WITH SITE LOCATION AND ARCHITECT'S DESIGN CRITERIA. |
| | PLEASE CORRELATE. |
| | |
| | 8. CONTRACTOR'S FLOOR PLAN CONFLICTS WITH ARCHITECT'S |
| | FLOOR PLAN, SEE PROXIMITY OF WINDOWS TO CORNER. IT |
| | APPEARS THAT WINDOWS ARE LOCATED IN ZONE 5. |
| | |
| | 9. PROVIDE MULLION PRODUCT APPROVAL FAC9B72. |
| | |
| | 10. DETAILS CIRCLED ON PRODUCT APPROVAL ARE APPLICABLE |
| | TO A BLOCK WALL. PLAN SHOWS A FRAME WALL. PLEASE |
| | CORRELATE. |
| | |
| | |