2011-01-07 10:50:12GAS REVIEW IS DENIED
  
 1) SHOW TYPE OF PIPING MATERIAL BEING INSTALLED, ALL
 PIPE SIZES, AND THE EDH NUMBER OF CORRUGATED STAINLESS
 STEEL TUBING FOR EACH PIPE SIZE AND SECTION OF PIPE.
  
 2) INDICATE THE DELIVERY PRESSURE (PSI) PER FBC-2007
 FUEL GAS SEC. 402.2. IF NATURAL GAS SPECIFY .5 PSI OR 2
 PSI.
  
 THE REQUIREMENTS FOR GAS PERMITS CAN BE FOUND AT THIS
 LINK. HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/GAS%20P
 ERMIT%20APPLICATION%20REQUIREMENTS.PDF
  