| Notes |
| Date |
Text |
| 2011-01-05 15:01:37 | PROVIDE A BONDING BAR AT THE SERVICE. NEC 250-94 | | | NOTE ON THE PLAN THE REQUIREMENT FOR TAMPER RESISTANT | | | RECEPTACLES. NEC 406.11 | | | THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2 | | | GFCI PROTECTED RECEPTACLE REQUIRED AT THE MECHANICAL | | | EQUIPMENT. NEC 210.63 | | | | | | ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718 | | | | | | |
|