| 2011-01-04 16:58:58 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. SITE PLAN AND MECHANICAL PLAN SHOW THE MECHANICAL |
| | EQUIPMENT AND SLAB ENCROACHING THE PROPERTY LINE. OTHER |
| | SHEETS SHOW THE MECHANICAL EQUIPMENT IN ANOTHER |
| | LOCATION. PLEASE CORRELATE. |
| | |
| | 2. PROVIDE OVERALL AND UNIT SIZE FOR THE ARCHED FIXED |
| | WINDOW, FAMILY ROOM. THE HEIGHT IS PROVIDED, NO WIDTH |
| | SHOWN FOR EITHER THE OVERALL OPENING OR FOR THE UNITS |
| | SEPARATED BY MULLIONS. FBC301. |
| | |
| | 3. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR |
| | THE ANCHORS SPECIFIED FOR THE MECHANICAL UNITS, |
| | FAC9B72. WIND RESISTANCE TO SLIDING AND OVERTURNING TO |
| | BE SHOWN AS WELL AS UPLIFT. |
| | |
| | 4. 1" AND 2" MULLION PRODUCT APPROVALS WERE SUBMITTED. |
| | PLEASE SPECIFY PROPOSED LOCATIONS. |
| | |
| | 5. SEE FBC R 1104.A.2, WALLS CONSIDERED CEILINGS. |
| | COFFERED CEILINGS NOT SHOWN ON CEILING SQUARE FOOT AREA |
| | ON ENERGY CALCS. |
| | |
| | 7. ENERGY CALC SHOWS TWO DIFFERENT TYPES OF FRAME WOOD |
| | ADJACENT WALLS (R11 AND R4.1), PLEASE SPECIFY ON PLAN. |
| | |
| | 8. PLEASE CHECK ALL ENERGY CALC ITEMS FOR CONSISTENCY |
| | WITH THE PLAN SUBMITTED. FOR INSTANCE, ROOF ON ENERGY |
| | CALC IS SHINGLE, PLAN SHOWS TILE. GARAGE CEILING HEIGHT |
| | ON PLAN IS 10', ENERGY CALC SHOWS 8'. ENERGY CALC SHOWS |
| | TWO EXTERIOR DOORS, EAST ORIENTATION. PLAN SHOWS ONE |
| | DOOR, WEST ORIENTATION. |
| | |
| | 9. SEE PREVIOUS COMMENT, AND ALSO NOTE THAT GARAGE |
| | FRAME WALL FACES WEST, ENERGY CALC SHOWS EAST |
| | ORIENTATION. PLEASE NOTE THAT ALTHOUGH THE SITE PLAN |
| | SHOWS "NORTH" ORIENTED TOWARDS THE TOP OF THE PAGE, |
| | ARCHITECTURAL SHEETS ARE REVERSED. NO "NORTH" |
| | DESIGNATION PROVIDED ON A SHEETS, BUT BASED ON THE SITE |
| | PLAN, "NORTH" WOULD BE THE BOTTOM OF THE PLAN. PLEASE |
| | CONFIRM ORIENTATION OF ALL ITEMS AND REVISE AS |
| | NECESSARY. |
| | |
| | |
| | |
| | PLAN SHOWS GARAGE FRAME WALL FACING WEST, ENERGY CALC |
| | SHOWS EAST. |
| | |
| | |
| | |
| | |
| | |