| Plan Review Notes For Permit 10120584 |
| Permit Number |
10120584 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-10 16:31:38 | RESIDENTIAL (R3) ADDITION, BUILDING REVIEW CHECKLIST. | | | 2007 FBC WITH 2009 REVISIONS. | | | | | | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES). SEC. N1100.0 | | | OF 2007 FLORIDA RESIDENTIAL CODE CHAPTER 11. PLEASE | | | MAKE SURE THE FORM IS COMPLETELY FILLED AND | | | CORRESPONDING SIGNATURES AT BOTTOM OF FORM ARE | | | PROVIDED. | | | | | | 2- ACCORDING TO 2009 REVISIONS SEC. R301.2.1.4.3 THIS | | | BUILDING IS LOCATED ON EXPOSURE "C" NOT "B". REVISE | | | INFORMATION ON SHEETS C1, S2.0 AND S3.0 AS REQUIRED. | | | REVISE THE DESIGN PRESSURES ACCORDINGLY. | | | | | | 3- BRING PLANS TO PALM BEACH COUNTY (2300 N. JOG RD) TO | | | VERIFY IF IMPACT FEES ARE DUE. BRING BACK STAMPED PLANS | | | AND COPY OF PAID RECEIPT IF FEES ARE DUE. | | | | | | 4- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY | | | DCA RULE 9B-72 FOR: | | | A) METAL ROOF AS SPECIFIED ON PLANS. | | | | | | B) PRECAST LINTELS AS SPECIFIED ON PLANS. | | | | | | 5- ARCHITECT TO REVIEW AND APPROVE IN WRITING (NOT | | | SIGNING AND SEALING) ALL PRODUCT APPROVALS AS REQUIRED | | | BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. | | | | | | 6- SPECIFY CARBON MONOXIDE ALARMS BY ALL BEDROOMS AS | | | REQUIRED BY SEC. R313.4 OF 2007 FLORIDA RESIDENTIAL | | | CODE. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|