| Plan Review Notes For Permit 10120582 |
| Permit Number |
10120582 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-12-29 14:05:34 | 1732--45TH STREET | | | PERMIT #10120582 | | | MASTER #10090025 | | | REVIEW COMMENTS - FIRE | | | | | | | | | INDICATE THE HAZARD CLASSIFICATION AND THE DESIGN | | | DENSITY OF THE SYSTEM. | | | | | | INDICATE IF THE EXPOSED STRUCTURE IS CONSIDERED | | | OBSTRUCTED OR UNOBSTRUCTED CONSTRUCTION. INDICATE THE | | | SPRINKLER DISTANCE BELOW THE ROOF DECK BASED UPON THE | | | CONSTRUCTION TYPE (OBSTRUCTED/UNOBSTRUCTED). | | | | | | THE SPRINKLER LOCATED IN WEST AREA OF THE STOREROOM IS | | | PROTECTING AN AREA GREATER THAN 130 SQUARE FEET. | | | | | | INDICATE THE MAXIMUM STORAGE/DISPLAY HEIGHT THAT IS | | | INTENDED FOR THIS RETAIL SPACE. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|