| Plan Review Notes For Permit 10120566 |
| Permit Number |
10120566 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-12-29 11:16:05 | 1 HARVARD CIRCLE | | | PERMIT #10120566 | | | MASTER #10090573 | | | REVIEW COMMENTS - FIRE | | | | | | BRANCH LINE (SUPPLYING NEW PENDENT SPRINKLER IN THE | | | STAIR) IS NOT PERMITTED TO BE ROUTED THROUGH THE | | | FIRE-RATED STAIR ENCLOSURE. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|