2011-01-05 10:54:34250 AUSTRALIAN AVENUE
 PERMIT NUMBER 10120530
  
  
 1. CARD READERS NOTED IN ELEVATORS, EXISTING WEST
 STAIR, AND EXISTING EAST VESTIBULE FOR EXIT STAIR. CARD
 READERS ARE NOT TO INTERFERE WITH EXITING. ACCORDING TO
 BUILDING AND FIRE CODES AT LEAST ONE EXIT IS TO BE
 ACCESSIBLE FROM THE ELEVATOR LOBBY. PLEASE SEE FLORIDA
 FIRE PREVENTION CODE, NFPA 101, SECTION 7.4.1.6. CARD
 READERS ARE NOT ALLOWED IN STAIRWELLS. PLEASE SEE
 FLORIDA FIRE PREVENTION CODE, NFPA 101, SECTION
 7.2.1.6.1 (6)
  
 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 3. NOTE # 17 IS INCORRECT ON PAGE E0.1. DUCT DETECTORS
 WHEN ACTIVATED SHALL CAUSE AN ALARM NOT A SUPERVISORY
 SIGNAL.
  
 4. EXIT SIGNS APPEAR TO BE MISSING FROM SHEET E3.1.
  
 5. IT APPEARS THAT ADDITIONAL FIRE ALARM DEVICES ARE
 NEEDED ON SHEET E3.1.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF