Plan Review Notes
Plan Review Notes For Permit 10120530
Permit Number 10120530
Review Stop B
Sequence Number 1
Notes
Date Text
2011-01-04 15:37:44BUILDING PLAN REVIEW
 PERMIT:10120530
 ADD: 250 S AUSTRALIAN AV# 1800
 CONT: PAVARIN INT.
 TEL: (954)903-3700
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET LS1.0 PLANS INDICATE CARD READERS WITH IN THE
 STAIRS PLEASE REVIEWFBC-B 1020.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT
 ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 712. THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 2) ELEVATOR LOBBIES VERSES CARD READERS. PLEASE PROVIDE
 ADDITIONAL INFORMATION ON THE CARD READERS AND
 COMPLIANCE WITH FBC-B 707.14.1 ELEVATOR LOBBIES SHALL
 HAVE AT LEAST ONE MEANS OF EGRESS COMPLYING WITH
 CHAPTER 10 AND OTHER PROVISIONS WITHIN THIS CODE.
  
 3) PLEASE PROVIDE DOCUMENTATION ON CARD READERS AND
 ELECTRIC LOCKS THAT THEY MEET TTHE REQUIREMENTS OF FBC
 1008.1.3.4.
  
 4) PLEASE REVIEW LS-1.0 11-4.13.6 MANEUVERING
 CLEARENCES AT DOORS. MINIMUM MANEUVERING CLEARANCES AT
 DOORS THAT ARE NOT AUTOMATIC OR POWER-ASSISTED SHALL BE
 AS SHOWN IN FIG. 25. THE FLOOR OR GROUND AREA WITHIN
 THE REQUIRED CLEARANCES SHALL BE CLEAR & LEVEL.
  
 5) SHEET A-1.1 GLAZED OPENINGS WITHIN WALLS: 2406.3
 HAZARDOUS LOCATIONS. THE FOLLOWING SHALL BE CONSIDERED
 SPECIFIC HAZARDOUS LOCATIONS REQUIRING SAFETY GLAZING
 MATERIALS: 6.GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE
 PANEL ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED EDGE
 OF THE GLAZING IS WITHIN A 24-INCH (610 MM) ARC OF
 EITHER VERTICAL EDGE OF THE DOOR IN A CLOSED POSITION
 AND WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS
 LESS THAN 60 INCHES (1524 MM) ABOVE THE WALKING
 SURFACE.
  
 6) SHEET A-4.0 RECEPTION DESK SECTION TO COMPLY WITH
 ACCESSIBILITY REQUIREMENTS:
  
 11-7.2 (2) AT TICKETING COUNTERS, TELLER STATIONS IN A
 BANK, REGISTRATION COUNTERS IN HOTELS AND MOTELS, BOX
 OFFICE TICKET COUNTERS, AND OTHER COUNTERS THAT MAY NOT
 HAVE A CASH REGISTER BUT AT WHICH GOODS OR SERVICES ARE
 SOLD OR DISTRIBUTED, EITHER:
  
 (I) A PORTION OF THE MAIN COUNTER WHICH IS A MINIMUM OF
 36 INCHES (915 MM) IN LENGTH SHALL BE PROVIDED WITH A
 MAXIMUM HEIGHT OF 36 INCHES (915 MM); OR
  
 (II) AN AUXILIARY COUNTER WITH A MAXIMUM HEIGHT OF 36
 IN (915 MM) IN CLOSE PROXIMITY TO THE MAIN COUNTER
 SHALL BE PROVIDED; OR
  
 (III) EQUIVALENT FACILITATION SHALL BE PROVIDED (E.G.,
 AT A HOTEL REGISTRATION COUNTER, EQUIVALENT
 FACILITATION MIGHT CONSIST OF:
  
 (1) PROVISION OF A FOLDING SHELF ATTACHED TO THE MAIN
 COUNTER ON WHICH AN INDIVIDUAL WITH DISABILITIES CAN
 WRITE, AND
  
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
  
  
  
  
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP