Plan Review Notes
Plan Review Notes For Permit 10120529
Permit Number 10120529
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2011-01-03 16:15:37250 AUSTRALIAN AVENUE
 PERMIT NUMBER 10120529
  
  
 1. CARD READERS DISPLAYED IN ELEVATOR LOBBIES, WITHIN
 EXISTING WEST EXIT STAIR, AND THE EXISTING VESTIBULE
 FOR THE EXISTING EAST STAIR. CARD READERS SHALL NOT
 INTERFERE WITH EXITING. ACCORDING TO BUILDING AND FIRE
 CODE REQUIREMENTS, AT LEAST ONE EXIT STAIR SHALL BE
 ACCESSIBLE FROM THE ELEVATOR LOBBY. PLEASE SEE FLORIDA
 FIRE PREVENTION CODE, NFPA 101, SECTION 7.4.1.6. CARD
 READERS ARE NOT ALLOWED TO BE INSTALLED IN EXIT
 STAIRWELLS. PLEASE SEE FLORIDA FIRE PREVENTION CODE,
 NFPA 101, SECTION 7.2.1.6.1 (6)
  
 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 3. PLEASE DESCRIBE LOCKING ARRANGEMENTS BEING USED
 WITHIN THIS SINGLE TENANT SPACE. ARE THE DOORS FAIL
 SAFE OR FAIL SECURE WHEN THE FIRE ALARM SYSTEM IS NOT
 ACTIVATED.
  
 4. ON SHEET E-2.1 EXIT SIGNS ARE MISSING THAT WERE
 SHOWN ON THE LIFE SAFETY PLAN. THIS SHEET DOES NOT
 CORRESPOND.
  
 5. ELEVATOR WARNING SIGNS ARE REQUIRED.
  
 6. SHEET A1.5 INDICATES THE 18TH FLOOR. THIS SHEET IS
 FROM ANOTHER PROJECT.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR PRE-ACTION
 FIRE SPRINKLER SYSTEM.
  
 8. NOTE # 17 ON PAGE E0.1 IS INCORRECT. DUCT DETECTORS
 TO CAUSE AN ALARM NOT A SUPERVISORY SIGNAL.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION