| Plan Review Notes For Permit 10120529 |
| Permit Number |
10120529 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-03 16:15:37 | 250 AUSTRALIAN AVENUE | | | PERMIT NUMBER 10120529 | | | | | | | | | 1. CARD READERS DISPLAYED IN ELEVATOR LOBBIES, WITHIN | | | EXISTING WEST EXIT STAIR, AND THE EXISTING VESTIBULE | | | FOR THE EXISTING EAST STAIR. CARD READERS SHALL NOT | | | INTERFERE WITH EXITING. ACCORDING TO BUILDING AND FIRE | | | CODE REQUIREMENTS, AT LEAST ONE EXIT STAIR SHALL BE | | | ACCESSIBLE FROM THE ELEVATOR LOBBY. PLEASE SEE FLORIDA | | | FIRE PREVENTION CODE, NFPA 101, SECTION 7.4.1.6. CARD | | | READERS ARE NOT ALLOWED TO BE INSTALLED IN EXIT | | | STAIRWELLS. PLEASE SEE FLORIDA FIRE PREVENTION CODE, | | | NFPA 101, SECTION 7.2.1.6.1 (6) | | | | | | 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | | | | 3. PLEASE DESCRIBE LOCKING ARRANGEMENTS BEING USED | | | WITHIN THIS SINGLE TENANT SPACE. ARE THE DOORS FAIL | | | SAFE OR FAIL SECURE WHEN THE FIRE ALARM SYSTEM IS NOT | | | ACTIVATED. | | | | | | 4. ON SHEET E-2.1 EXIT SIGNS ARE MISSING THAT WERE | | | SHOWN ON THE LIFE SAFETY PLAN. THIS SHEET DOES NOT | | | CORRESPOND. | | | | | | 5. ELEVATOR WARNING SIGNS ARE REQUIRED. | | | | | | 6. SHEET A1.5 INDICATES THE 18TH FLOOR. THIS SHEET IS | | | FROM ANOTHER PROJECT. | | | | | | 7. SEPARATE PLANS AND PERMITS REQUIRED FOR PRE-ACTION | | | FIRE SPRINKLER SYSTEM. | | | | | | 8. NOTE # 17 ON PAGE E0.1 IS INCORRECT. DUCT DETECTORS | | | TO CAUSE AN ALARM NOT A SUPERVISORY SIGNAL. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|