| 2011-01-04 14:11:31 | BUILDING PLAN REVIEW |
| | PERMIT:10120529 |
| | ADD: 250 S AUSTRALIAN AV# 1700 |
| | CONT: PAVARIN INT. |
| | TEL: (954)903-3700 |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET LS1.0 PLANS INDICATE CARD READERS WITH IN THE |
| | STAIRS PLEASE REVIEWFBC-B 1020.1.2 PENETRATIONS. |
| | PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT |
| | ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT |
| | DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT |
| | PRESSURIZATION, SPRINKLER PIPING, STANDPIPES, |
| | ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION |
| | SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT |
| | ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING |
| | 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE |
| | PROTECTED IN ACCORDANCE WITH SECTION 712. THERE SHALL |
| | BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER |
| | PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES. |
| | |
| | 2) ELEVATOR LOBBIES VERSES CARD READERS. PLEASE PROVIDE |
| | ADDITIONAL INFORMATION ON THE CARD READERS AND |
| | COMPLIANCE WITH FBC-B 707.14.1 ELEVATOR LOBBIES SHALL |
| | HAVE AT LEAST ONE MEANS OF EGRESS COMPLYING WITH |
| | CHAPTER 10 AND OTHER PROVISIONS WITHIN THIS CODE. |
| | |
| | 3) PLEASE PROVIDE DOCUMENTATION ON CARD READERS AND |
| | ELECTRIC LOCKS THAT THEY MEET TTHE REQUIREMENTS OF FBC |
| | 1008.1.3.4. |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |