| Plan Review Notes For Permit 10120509 |
| Permit Number |
10120509 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-04 15:39:22 | 250 AUSTRALIAN AVENUE | | | PERMIT NUMBER 10120509 | | | | | | | | | 1. CARD READERS DISPLAYED IN ELEVATOR LOBBIES WITHIN | | | EXISTING WEST STAIR, AND THE EXISTING VESTIBULE FOR THE | | | EXISTING EAST STAIR. CARD READERS SHALL NOT INTERFERE | | | WITH EXITING. ACCORDING TO BUILDING AND FIRE CODE | | | REQUIREMENTS, AT LEAST ONE STAIR SHALL BE ACCESSIBLE | | | FROM THE ELEVATOR LOBBY. PLEASE SEE FLORIDA FIRE | | | PREVENTION CODE, NFPA 101, SECTION 7.4.1.6. CARD | | | READERS ARE NOT TO BE INSTALLED IN THE EXIT STAIRWELLS. | | | PLEASE SEE FLORIDA FIRE PREVENTION CODE, NFPA 101, | | | SECTION 7.2.1.6.1. | | | | | | 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | | | | 3. PLEASE DESCRIBE LOCKING ARRANGEMENTS BEING USED | | | WITHIN THIS SINGLE TENANT SPACE. ARE DOORS FAIL SAFE OR | | | FAIL SECURE WHEN THE FIRE ALARM SYSTEM IS NOT | | | ACTIVATED. | | | | | | 4. ON SHEET E2.1 EXIT SIGNS ARE MISSING THAT WERE SHOWN | | | ON THE LIFE SAFETY PLAN. THIS SHEET DOES NOT | | | CORRESPOND. | | | | | | 5. ELEVATOR WARNING SIGNS ARE REQUIRED. | | | | | | 6. SHEET A1.5 INDICATES THE 18TH FLOOR. PLAN SHEET DOES | | | NOT CORRESPOND. | | | | | | 7. SEPARATE PLANS AND PERMITS REQUIRED FOR PRE-ACTION | | | FIRE SPRINKLER SYSTEM. | | | | | | 8. NOTE # 17 ON PAGE E0.1 IS INCORRECT. DUCT DETECTORS | | | TO CAUSE AN ALARM NOT A SUPERVISORY SIGNAL. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|