2011-01-04 15:39:22250 AUSTRALIAN AVENUE
 PERMIT NUMBER 10120509
  
  
 1. CARD READERS DISPLAYED IN ELEVATOR LOBBIES WITHIN
 EXISTING WEST STAIR, AND THE EXISTING VESTIBULE FOR THE
 EXISTING EAST STAIR. CARD READERS SHALL NOT INTERFERE
 WITH EXITING. ACCORDING TO BUILDING AND FIRE CODE
 REQUIREMENTS, AT LEAST ONE STAIR SHALL BE ACCESSIBLE
 FROM THE ELEVATOR LOBBY. PLEASE SEE FLORIDA FIRE
 PREVENTION CODE, NFPA 101, SECTION 7.4.1.6. CARD
 READERS ARE NOT TO BE INSTALLED IN THE EXIT STAIRWELLS.
 PLEASE SEE FLORIDA FIRE PREVENTION CODE, NFPA 101,
 SECTION 7.2.1.6.1.
  
 2. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS.
  
 3. PLEASE DESCRIBE LOCKING ARRANGEMENTS BEING USED
 WITHIN THIS SINGLE TENANT SPACE. ARE DOORS FAIL SAFE OR
 FAIL SECURE WHEN THE FIRE ALARM SYSTEM IS NOT
 ACTIVATED.
  
 4. ON SHEET E2.1 EXIT SIGNS ARE MISSING THAT WERE SHOWN
 ON THE LIFE SAFETY PLAN. THIS SHEET DOES NOT
 CORRESPOND.
  
 5. ELEVATOR WARNING SIGNS ARE REQUIRED.
  
 6. SHEET A1.5 INDICATES THE 18TH FLOOR. PLAN SHEET DOES
 NOT CORRESPOND.
  
 7. SEPARATE PLANS AND PERMITS REQUIRED FOR PRE-ACTION
 FIRE SPRINKLER SYSTEM.
  
 8. NOTE # 17 ON PAGE E0.1 IS INCORRECT. DUCT DETECTORS
 TO CAUSE AN ALARM NOT A SUPERVISORY SIGNAL.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION