2011-01-04 14:20:58BUILDING PLAN REVIEW
 PERMIT:10120509
 ADD: 250 S AUSTRALIAN AV# 800
 CONT: PAVARIN INT.
 TEL: (954)903-3700
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET LS1.0 PLANS INDICATE CARD READERS WITH IN THE
 STAIRS PLEASE REVIEWFBC-B 1020.1.2 PENETRATIONS.
 PENETRATIONS INTO AND OPENINGS THROUGH AN EXIT
 ENCLOSURE ARE PROHIBITED EXCEPT FOR REQUIRED EXIT
 DOORS, EQUIPMENT AND DUCTWORK NECESSARY FOR INDEPENDENT
 PRESSURIZATION, SPRINKLER PIPING, STANDPIPES,
 ELECTRICAL RACEWAY FOR FIRE DEPARTMENT COMMUNICATION
 SYSTEMS AND ELECTRICAL RACEWAY SERVING THE EXIT
 ENCLOSURE AND TERMINATING AT A STEEL BOX NOT EXCEEDING
 16 SQUARE INCHES (0.010 M2). SUCH PENETRATIONS SHALL BE
 PROTECTED IN ACCORDANCE WITH SECTION 712. THERE SHALL
 BE NO PENETRATIONS OR COMMUNICATION OPENINGS, WHETHER
 PROTECTED OR NOT, BETWEEN ADJACENT EXIT ENCLOSURES.
  
 2) ELEVATOR LOBBIES VERSES CARD READERS. PLEASE PROVIDE
 ADDITIONAL INFORMATION ON THE CARD READERS AND
 COMPLIANCE WITH FBC-B 707.14.1 ELEVATOR LOBBIES SHALL
 HAVE AT LEAST ONE MEANS OF EGRESS COMPLYING WITH
 CHAPTER 10 AND OTHER PROVISIONS WITHIN THIS CODE.
  
 3A) SHEET A-1.2 THE SERVER ROOM # 806. THE PLANS
 INDICATE THE WALS TO BE EXISTING, BUT IS THIS A TRUE IT
 ROOM REQUIRING 1 HOUR RATED WALLS PER NEC 645.4(5) ? IF
 THE WALLS REQUIRE THE FIRE RATING DO THE WALLS EXTEND
 UP ALL THE WAY TO THE DECK ABOVE?
  
 3B) IS THE RAISED FLOOR EXISTING OR NEW? IF NEW PLEASE
 PROVIDE DESIGN CRITERIA IN REGARDS TO FLOOR LOADING,
 LIVE LOADS, TYPE OF FLOOR SYSTEM AND FIRE RESISTANCE,
 IS THIS A PLASTIC TYPE OR COMPOSITE MATERIAL?
  
 3C) IF THE RAISED FLOORING IS NEW PLEASE PROVIDE
 INFORMATION ON THTE ACCESSIBLE RAMP,FBC-B 707.14.1
 ELEVATOR LOBBIES SHALL HAVE AT LEAST ONE MEANS OF
 EGRESS COMPLYING WITH CHAPTER 10 AND OTHER PROVISIONS
 WITHIN THIS CODE. 11-4.8.4.(2) LANDINGS. THE BOTTOM OF
 EACH RAMP SHALL HAVE NOT LESS THAN 72" OF STRAIGHT &
 LEVEL CLEARANCE.
  
 4) SHEET A-1.4 IT APPEARS THAT THERE IS WORK BEING
 COMPLETED OUTSIDE OF THE TENANT AREA, BUT WITHIN THE
 COMMON AREAS?
  
 5) SHEET A-1.5 IT APPEARS THIS SHEET WAS MISTAKENLY
 APPLIED TO THIS PROJECT, PLANS INDICATE 18TH FLOOR
 EQUIPMENT PLAN.
 106.1.2 ADDITIONAL INFORMATION REQUIRED.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  