Notes
Date Text
2011-01-31 09:14:49****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. REVISE PLAN TO SHOW TYPE OF OPENING (DOOR OR
 WINDOW), FBC1003.6. IF YOU PROPOSE TO COVER REQUIRED
 EXIT DOORS WITH SHUTTERS, PROVIDE A LIFE SAFETY PLAN
 WHICH SHOWS THE FOLLOWING INFORMATION:
  
 OVERALL BUILDING DIMENSIONS
 OCCUPANCY CLASSIFICATION FBC CHAPTER 3
 EXITING INFORMATION
  
 2. ADDRESSED.
  
 3. COMPLETE THE SAMPLE INSTALLATION SCHEDULE OR PROVIDE
 ALL INFORMATION TO SHOW CODE COMPLIANCE IN ANOTHER
 FORMAT, FBC*106, FBC R301, FBC1609. TWO SETS REQUIRED.
 THIS FORM IS AVAILABLE IN THE LOBBY OR ON THE INTERNET
 AT
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/PDF/SCHEDULE_FOR_
 INSTALLATION.PDF
  
 4. ADDRESSED.
  
  
  
 FBC 1003.6, MEANS OF EGRESS CONTINUITY. THE PATH OF
 EGRESS TRAVEL ALONG A MEANS OF EGRESS SHALL NOT BE
 INTERRUPTED BY ANY BUILDING ELEMENT OTHER THAN A MEANS
 OF EGRESS COMPONENT AS SPECIFIED IN THIS CHAPTER.
 OBSTRUCTIONS SHALL NOT BE PLACED IN THE REQUIRED WIDTH
 OF A MEANS OF EGRESS EXCEPT PROJECTIONS PERMITTED BY
 THIS CHAPTER.
  
 1008.1.3.5 SECURITY GRILLS. IN GROUPS B, F, M, R AND S,
 HORIZONTAL SLIDING OR VERTICAL SECURITY GRILLES ARE
 PERMITTED AT THE MAIN EXIT AND SHALL BE OPENABLE FROM
 THE INSIDE WITHOUT THE USE OF A KEY OR SPECIAL
 KNOWLEDGE OR EFFORT DURING PERIODS THAT THE SPACE IS
 OCCUPIED. THE GRILLES SHALL REMAIN SECURED IN THE
 FULL-OPEN POSITION DURING THE PERIOD OF OCCUPANCY BY
 THE GENERAL PUBLIC. WHERE TWO OR MORE MEANS OF EGRESS
 ARE REQUIRED, NOT MORE THAN ONE-HALF OF THE EXITS OR
 EXIT ACCESS DOORWAYS SHALL BE EQUIPPED WITH HORIZONTAL
 SLIDING OR VERTICAL SECURITY GRILLES.
  