2011-04-14 11:27:21BUILDING PLAN REVIEW
 PERMIT: 10120482
 ADD: 7620 S DIXIE HWY
 CONT: STRIKE CONSULTING INC.
 TEL: (561)644-1887
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
  
 1-2) COMPLIED.
  
 3) THE PLANS INDICATE THE INSTALATION OF NEW STORE
 FRONT SYSTEM, AND STEMWALL CONSTRUCTION:
 3A-C) COMPLIED
  
 3D) 2ND REQUEST, RESPONCE COMMENTS INDICATE THE PRODUCT
 APPROVALS THAT WERE TO BE SUBMITTED ARE TO BE LARGE
 MISSILE IMPACT. THE STOREFRONT DOOR AND AND STOREFRONT
 SYSTEM SUBMITTED (NOA 06-0818.02/ NOA 08-1024.07) BOTH
 ARE NON-IMPACT GLAZING.
  
 THE SECOND ISSUE WITH THE STOREFRONT SYSTEM CHART# 2
 THE DESIGN LOAD CAPACITY OF THE GLASS SIZE EXCEEDS THE
 TABLES.
  
 THE THIRD ISSUE IS THE MULLION CAPACITY HAS BEEN
 EXCEEDED FOR BOTH SPACING AND HEIGHT VERSES THE PLANS
 INDICATING THE FRONT STOREFRONT WINDOW UNITS TO BE 6
 FEET WIDE.
  
 THE FOURTH ISSUE WITH THE SUBMITTED PRODUCT APPROVALS,
 ONLY ONE SET OF APPROVALS WERE SUBMITTED FOR NOA
 09-23.09 & 11-0128.03.
 NOTE ON THE ORIGINAL REVIEW ONE SET OF NON-IMPACT
 PRODUCT APPROVALS WERE SUBMITTED FOR STOREFRONT GLAZING
 AND DOOR WITH TRANSOM NON-IMPACT, WITH THE FIRST
 RE-SUBMITTAL THE 2ND SET WERE SUBMITTED, NON-IMPACT
 GLAZING ALSO.
  
 FROM 1ST REVIEW, SHEET A100 ALSO INDICATE THE REUSE OF
 EXISTING SHUTTERS, THE CITY RECORDS DOESN'T INDICATE
 ANY PERMIT WAS EVER PULLED FOR THE INSTALLATION OF
 THESE SHUTTERS NOR CAN THE TESTING FOR LARGE MISSILE
 IMPACT TESTING. 1609.1.4 PROTECTION OF OPENINGS IN
 WIND-BORNE DEBRIS REGIONS, EXTERIOR GLAZING THAT
 RECEIVES POSITIVE PRESSURE IN THE LOWER 60 FEET (18.3
 M) IN BUILDINGS SHALL BE ASSUMED TO BE OPENINGS AND THE
 BALANCE OF GLAZED OPENINGS IN THE REST OF THE BUILDING
 SHALL BE ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT
 RECEIVES POSITIVE PRESSURE IS IMPACT RESISTANT OR
 PROTECTED WITH AN IMPACT RESISTANT COVERING MEETING THE
 REQUIREMENTS OF SSTD 12, ASTM E 1886 AND ASTM E 1996,
 OR MIAMI-DADE TAS 201, 202 AND 203 REFERENCED THEREIN
 AS FOLLOWS: 1. GLAZED OPENINGS LOCATED WITHIN 30 FEET
 (9.1 M) OF GRADE SHALL MEET THE REQUIREMENTS OF THE
 LARGE MISSILE .
  
 4-5) COMPLIED.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  