1 |
|
| Notes |
| Date |
Text |
| 2010-12-29 13:13:32 | 7620 SOUTH DIXIE HIGHWAY | | | PERMIT NUMBER 10120482 | | | "REPLACE STOREFRONT, INSTALL HVAC UNIT, FIX BATHROOMS, | | | MAKE ADA, INSTALL DOORS | | | | | | | | | 1) ADDITIONAL EXIT SIGNS ARE NEEDED; ONE NEAR THE | | | DOUBLE DOORS LEADING FROM THE EXISTING RETAIL TO THE | | | EXISTING ENVELOPE, AND FROM THE DRAWING TO DIRECT | | | PERSONS FROM THE STORAGE AREA AS IT APPEARS THAT NO | | | SEPARATION EXISTS. | | | | | | 2. PLEASE PROVIDE A FIXTURE PLAN. IN CLASS C MERCANTILE | | | OCCUPANCIES, A SINGLE MEANS OF EGRESS IS PERMITTED AS | | | LONG AS THE TRAVEL DISTANCE DOES NOT EXCEED 75 FEET. | | | PLEASE ILLUSTRATE FIXTURES AND TRAVEL DISTANCE TO THE | | | SINGLE EXIT. | | | | | | 3. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR | | | WALLS AND CEILINGS. | | | | | | 4. TACTILE SIGNAGE REQUIRED AT EXIT DOOR. | | | | | | 5. THE PLANS DO NOT INDICATE THE LOCATIONS OF ANY | | | EXISTING OR NEW PORTABLE FIRE EXTINGUISHERS. | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|