Plan Review Notes
Plan Review Notes For Permit 10120482
Permit Number 10120482
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-12-29 13:13:327620 SOUTH DIXIE HIGHWAY
 PERMIT NUMBER 10120482
 "REPLACE STOREFRONT, INSTALL HVAC UNIT, FIX BATHROOMS,
 MAKE ADA, INSTALL DOORS
  
  
 1) ADDITIONAL EXIT SIGNS ARE NEEDED; ONE NEAR THE
 DOUBLE DOORS LEADING FROM THE EXISTING RETAIL TO THE
 EXISTING ENVELOPE, AND FROM THE DRAWING TO DIRECT
 PERSONS FROM THE STORAGE AREA AS IT APPEARS THAT NO
 SEPARATION EXISTS.
  
 2. PLEASE PROVIDE A FIXTURE PLAN. IN CLASS C MERCANTILE
 OCCUPANCIES, A SINGLE MEANS OF EGRESS IS PERMITTED AS
 LONG AS THE TRAVEL DISTANCE DOES NOT EXCEED 75 FEET.
 PLEASE ILLUSTRATE FIXTURES AND TRAVEL DISTANCE TO THE
 SINGLE EXIT.
  
 3. PLEASE INDICATE INTERIOR FINISH CLASSIFICATIONS FOR
 WALLS AND CEILINGS.
  
 4. TACTILE SIGNAGE REQUIRED AT EXIT DOOR.
  
 5. THE PLANS DO NOT INDICATE THE LOCATIONS OF ANY
 EXISTING OR NEW PORTABLE FIRE EXTINGUISHERS.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION