| 2011-01-05 12:09:48 | BUILDING PLAN REVIEW |
| | PERMIT: 10120482 |
| | ADD: 7620 S DIXIE HWY |
| | CONT: STRIKE CONSULTING INC. |
| | TEL: (561)644-1887 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS ARE INDICATED TO BE DESIGNED BY A FLORIDA |
| | REGISTERED ARCHITECT BUT THERE IS ALSO A YANG DESIGN |
| | GROUP, INC ON THE TITLE BLOCK WITH NO FLORIDA LICENSE |
| | NUMBER PLEASE REVIEW FL S S 481. 223 LICENSURE |
| | REQUIREMENTS FOR INTERIOR DESIGN. |
| | |
| | 2) THE NEW STORE CONFIGURATION INDICATED ON SHEET A100 |
| | INDICATES A SINGLE EXIT DESIGN FOR THE WHOLE BUILDING, |
| | PLEASE PROVIDE A LIFE SAFETY PLAN FOR EGRESS TRAVEL |
| | FROM THE MOST REMOTE POINT IN THE BUILDING, INCLUDE ANY |
| | KIOSK, STANDS THAT WILL IMPEDE EGRESS. THE |
| | SINGLE EXIT IS LIMITED IN MERCANTILE OCCUPANCY TO 30 |
| | OCCUPANTS AND TRAVEL DISTANCE OF 75'-0". PLEASE PROVIDE |
| | THE OCCUPANT LOAD FOR THE TOTAL MERCANTILE SQ FOOTAGE, |
| | I BELIEVE YOU WILL SEE IT EXCEEDS 30 WHEN USING 30 SQ |
| | FT / OCCUPANT. SEE FBC-B TABLE 1019.2 & |
| | TABLE 1004.1.1 REQUIRING A MINIMUM OF TWO EXITS. PLEASE |
| | NOTE ALSO EGRESS DOORS ARE TO BE SIDE SWING DOORS, TTHE |
| | OVERHEAD DOORS WILL NOT MEET THE EXCEPTIONS FOR THIS |
| | OCCUPANCY CLASSIFICATION AND LOAD. |
| | |
| | 3) THE PLANS INDICATE THE INSTALATION OF NEW STORE |
| | FRONT SYSTEM, AND STEMWALL CONSTRUCTION: |
| | 3A) PLANS ARE DEFICIENT IN PROVIDING WIND DESIGN |
| | CRITERIA:1609.6.2 WIND DESIGN PROCEDURES |
| | 1) THE BASIC WIND SPEED, V, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION 1609.3. THE WIND SHALL BE |
| | ASSUMED TO COME |
| | FROM ANY HORIZONTAL DIRECTION. |
| | 2) AN IMPORTANCE FACTOR, IW, SHALL BE DETERMINED IN |
| | ACCORDANCE WITH SECTION1609.5. |
| | 3) AN EXPOSURE CATEGORY SHALL BE DETERMINED IN |
| | ACCORDANCE WITH 1609.4. NOTE "C" EXPOSURE |
| | 4) A HEIGHT AND EXPOSURE ADJUSTMENT COEFFICIENT, * |
| | SHALL BE DETERMINED FROM TABLE 1609.6.2.1(4) |
| | 5) POSITIVE & NEGATIVE DESIGN PRESSURES FOR INTERIOR |
| | ZONES(4) AND END ZONES(5). |
| | |
| | 3B) PLANS A100 ALSO INDICATE A NEW KNEE WALL, PLEASE |
| | PROVIDE DESIGN FOR PART OF THE MWFRS, INCLUDING STEEL |
| | IMBEDMENT, SIZE OF REBAR & SPACING. ALSO PROVIDE THE |
| | MINIMUM DESIGN MIX FOR CONCRETE OR GROUT MIX. |
| | |
| | 3C) 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH ARE |
| | REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED AND |
| | APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR TO |
| | SUBMITTAL FOR JURISDICTIONAL APPROVAL. |
| | |
| | 3D) SHEET A100 ALSO INDICATE THE REUSE OF EXISTING |
| | SHUTTERS, THE CITY RECORDS DOESN'T INDICATE ANY PERMIT |
| | WAS EVER PULLED FOR THE INSTALLATION OF THESE SHUTTERS |
| | NOR CAN THE TESTING FOR LARGE MISSILE IMPACT TESTING. |
| | 1609.1.4 PROTECTION OF OPENINGS IN WIND-BORNE DEBRIS |
| | REGIONS, EXTERIOR GLAZING THAT RECEIVES POSITIVE |
| | PRESSURE IN THE LOWER 60 FEET (18.3 M) IN BUILDINGS |
| | SHALL BE ASSUMED TO BE OPENINGS AND THE BALANCE OF |
| | GLAZED OPENINGS IN THE REST OF THE BUILDING SHALL BE |
| | ASSUMED TO BE ZERO UNLESS SUCH GLAZING THAT RECEIVES |
| | POSITIVE PRESSURE IS IMPACT RESISTANT OR PROTECTED WITH |
| | AN IMPACT RESISTANT COVERING MEETING THE REQUIREMENTS |
| | OF SSTD 12, ASTM E 1886 AND ASTM E 1996, OR MIAMI-DADE |
| | TAS 201, 202 AND 203 REFERENCED THEREIN AS FOLLOWS: 1. |
| | GLAZED OPENINGS LOCATED WITHIN 30 FEET (9.1 M) OF GRADE |
| | SHALL MEET THE REQUIREMENTS OF THE LARGE MISSILE . |
| | |
| | 4) SHEET A100 INDICATES A NEW DOOR OPENING CUT INTO A |
| | BLOCK WALL BUT NO INFORMATION IS PROVIDED ON COLUMNS |
| | AND EITHER BEAM OR LINTEL TO HOLD THE REMAINDER OF |
| | BLOCK WORK IN PLACE. |
| | |
| | 5) SHEET A100 WITHIN THE NEWLY A/C SPACE THE PLANS |
| | INDICATE A NEWLY TILE FLOOR PLEASE PROVIDE DETAIL FOR |
| | THE NEW CHANGE IN ELEVATION FROM THE REMAINDER OF THE |
| | FLOOR. FBC-B 11-4.3.8. |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |
| | E-MAIL: [email protected] |
| | |