| 2010-12-28 10:26:09 | ****CORRECTIONS**** |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | 561-805-6724 [email protected] |
| | FBC FLORIDA BUILDING CODE 2007 |
| | FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL |
| | |
| | 1. PROVIDE STRUCTURAL INFORMATION REGARDING THE FRAMES, |
| | FBC1609. I WAS UNABLE TO LOCATE EVIDENCE OF A PERMIT |
| | FOR THE "EXISTING STRUCTURE." |
| | |
| | 2. IF THE AWNING AND CANOPIES ARE TO BE DESIGNED TO |
| | FBC3105.4, PROVIDE AWNING FABRIC REMOVAL INSTRUCTIONS |
| | TO SHOW COMPLIANCE WITH FBC3105.4.2.1, QUICK RELEASE. |
| | THE PHOTOGRAPHS PROVIDED ARE NOT LABELED SO THE |
| | SEQUENCE CANNOT BE DETERMINED. ALSO THE METHOD |
| | SUBMITTED IS NOT A METHOD WHICH HAS BEEN DEMONSTRATED |
| | TO COMPLY WITH THE REQUIREMENT OF "QUICK RELEASE." TWO |
| | COMPLETE SETS OF PERMIT DOCUMENTS ARE REQUIRED FOR |
| | PERMIT ISSUANCE. |
| | |
| | 3. IF THE STRUCTURE IS TO BE DESIGNED PER FBC3105.4.2, |
| | PER BUILDING OFFICIAL, WE ARE TO PUT ON THE PERMIT FILE |
| | A LETTER, OR CONTRACTORS FORM, SIGNED BY THE OWNER (NOT |
| | THE TENANT) TO ACKNOWLEDGE THEIR RESPONSIBILITY TO HAVE |
| | THE AWNING COVER REMOVED PRIOR TO ANY WIND EVENT WITH |
| | PROJECTED WIND SPEEDS OF 75 MPH OR GREATER. THE |
| | LETTER/FORM MUST BE SIGNED BY THE OWNER BUT IT NEED NOT |
| | BE NOTARIZED. |
| | |
| | 4. OUR RECORDS SHOW AN EXPIRED SIGN PERMIT APPLICATION, |
| | 06100924. PLEASE ADDRESS. |
| | |
| | |
| | |
| | |