| 2010-12-27 14:53:00 | BEDROOM RECEPTACLES MUST BE PROTECTED WITH AFCI'S. NEC | | | 210.12 | | | PROVIDE A BONDING BAR AT THE SERVICE. NEC 250-94 | | | THE SMOKE DETECTORS MUST BE INTERCONNECTED. FBC R313.2 | | | TAMPER -RESISTANCE RECEPTACLES REQUIRED. NEC 406.11, | | | 210.52 | | | PROVIDE A RISER DIAGRAM. INDICATE THE SIZE OF THE | | | EXISTING SERVICE, FEEDERS AND MAIN DISCONNECT. |
|