Plan Review Notes
Plan Review Notes For Permit 10120470
Permit Number 10120470
Review Stop B
Sequence Number 1
Notes
Date Text
2010-12-27 10:14:11****CORRECTIONS****
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
 FBC FLORIDA BUILDING CODE 2007
 FBC R FLORIDA BUILDING CODE 2007 RESIDENTIAL
  
 1. PROVIDE A ROOM DESIGNATION FOR THE AREA ADJACENT TO
 THE PROPOSED NEW RESTROOM 100. SEE FBC 708.1(7), IT
 APPEARS THAT A FIRE PARTITION IS REQUIRED BUT WALL TYPE
 W1 IS NOT A RATED WALL.
  
 2. PROVIDE FLORIDA STATE OR LOCAL PRODUCT APPROVAL FOR
 THE EXHAUST GRILL, FAC9B72.
  
 3. REVISE PLAN TO INCLUDE DESIGN PRESSURES FOR THE
 SOFFIT EXHAUST GRILL, FBC1609.1, ALL EXTERIOR SOFFITS
 SHALL BE CAPABLE OF RESISTING THE DESIGN PRESSURES
 SPECIFIED FOR COMPONENTS AND CLADDING LOADS.
  
 4. PROVIDE A BLOCKING DETAIL OR SPECIFICATION, SEE FBC
 602.2, 603. DESIGN INTENT IS NOT CLEAR; PLEASE NOTE
 THAT THIS IS A NONCOMBUSTIBLE BUILDING AND NO
 INFORMATION PROVIDED REGARDING THE BLOCKING REFERRED TO
 IN RESTROOM ACCESSORIES NOTE, SHEET A1.1.
  
 5. PLEASE NOTE THAT, IF ALL OTHER TRADES PASS REVIEW,
 THIS REVIEW CAN BE PASSED WITH PROVISO UPON DESIGNER'S
 REQUEST.
  
  