| Plan Review Notes For Permit 10120466 |
| Permit Number |
10120466 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-12-20 09:14:33 | LOCATE SMOKE DETECTORS ON THE PLAN. INDICATE THEY ARE | | | TO BE INTERCONNECTED. FBC 907.2.10 | | | SHOW LOCATION OF EXISTING PANEL BOARD. PROVIDE SIZE AND | | | RATING OF THE NEW PANEL BOARD. SHOW EXISTING SERVICE | | | WIRE SIZE AND OVERCURRENT PROTECTION PROVIDED AT THE | | | MAIN SERVICE DISTRIBUTION. PROVIDE A PANEL SCHEDULE | | | SHOWING ALL CIRCUITS NEW AND EXISTING WITH CIRCUIT | | | BREAKERS AND WIRE SIZES. NEC 210.2, 230.3, 240.4 | | | | | | ROBERT LECKY, PLANS EXAMINER, 561-805-6718 | | | | | | |
|