| 2011-01-06 15:00:12 | RESIDENTIAL (R3) ALTERATION BUILDING REVIEW CHECKLIST. |
| | 2007 FBC WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13 |
| | FLORIDA STATUTE. |
| | ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK |
| | UP. |
| | |
| | 2- ENGINEER WHO PREPARED THE DRAWINGS TO SIGN, SEAL AND |
| | DATE ALL DRAWINGS AS REQUIRED BY CHAPTER 471 FLORIDA |
| | STATUTES. |
| | |
| | 3- CONTRACTOR SHOWN ON THE DRAWINGS TITLE BLOCK DOESN'T |
| | MATCH CONTRACTOR SHOWN ON THE PERMIT APPLICATION. |
| | REVISE AS REQUIRED TO MATCH. |
| | |
| | 4- SPECIFY CARBON MONOXIDE ALARMS AS REQUIRED BY SEC. |
| | R313.4 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 5- SPECIFY SMOKE ALARMS AS REQUIRED BY SEC. R313.2.1. |
| | |
| | 6- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9B-72 FOR: |
| | A) SINGLE HUNG WINDOWS AS SHOWN ON PLANS. |
| | B) WINDOW MULLIONS AS SHOWN ON PLANS. |
| | C) ROOF TILE. |
| | D) ROOF TILE ADHESIVE. |
| | E) FLAT ROOF. AND PROVIDE RAS 117 CALCULATIONS FOR NAIL |
| | ENHANCING AT PERIMETER AND CORNER AREAS. IF GENERAL |
| | LIMITATION #7 ON LAST PAGE OF NOA REQUIRES SIGNED AND |
| | SEALED RAS 117 CALCULATIONS, THEN, CALCULATIONS NEED TO |
| | BE SIGNED AND SEALED. |
| | ***NOTE: DESIGN PROFESSIONAL DOING THE RAS 117 |
| | CALCULATIONS TO TAKE INTO CONSIDERATION THAT THIS |
| | BUILDING IS CONSIDERED EXPOSURE "C". |
| | |
| | F) HURRICANE SHUTTERS. AND , PROVIDE COMPLETE |
| | INSTALLATION SCHEDULE. HURRICANE OPENING PROTECTION IS |
| | REQUIRED FOR THE 2 SINGLE HUNG WINDOWS AND FRENCH DOOR. |
| | |
| | 7- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS. SEC. |
| | 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 8- PROVIDE COMPLETE DETAIL SECTION AND SPECIFICATIONS |
| | FOR GABLE END ROOF TO SHOW COMPLIANCE WITH SEC. R609.4 |
| | OF 2007 FLORIDA RESIDENTIAL CODE. |
| | |
| | 9- PROVIDE COMPLETE DETAILS, SECTION AND SPECIFICATIONS |
| | FOR NEW ENTRY STEPS AT NEW ENTRY PORCH TO SHOW |
| | COMPLIANCE WITH SEC. R311.5.3. |
| | |
| | 10- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. VALUATION TO INCLUDE ALL LABOR, MATERIALS AND |
| | ENGINEERING FEES. REVISE AS REQUIRED. SEC. 108.3 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 11-SHEET #1: |
| | A) UP[DATE GENERAL NOTE #1. REFER TO 2007 FLORIDA |
| | RESIDENTIAL CODE. |
| | |
| | B) REVISE GENERAL NOTE #26. ROOF ZONE #3 REQUIRES |
| | NAILING AT 4" O.C. NOT ONLY THE GABLE ENDS. SEE SEC. |
| | R803.2.3.1. |
| | |
| | C) REVISE DESIGN CRITERIA. ACCORDING TO THE 2009 |
| | REVISIONS SEC. R301.2.1.4.3 THIS BUILDING IS LOCATED ON |
| | EXPOSURE "C" NOT "B". ALSO, REVISE THE DESIGN PRESSURES |
| | ACCORDINGLY. |
| | |
| | 12- SECTION "B" ON SHEET #3: THE WIRE LATH ATTACHMENT |
| | NOTE SPECIFIES 1 1/2"LONG NAILS. ASTM C 1063 REQUIRES 1 |
| | 3/4" MIN. NAIL PENETRATION INTO HORIZONTAL WOOD FRAMING |
| | MEMBER. SEC. R703.6 OF 2007 FLORIDA RESIDENTIAL CODE. |
| | REVISE SIZE OF NAIL AS REQUIRED BY ASTM C1063. |
| | |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |
| | |
| | |
| | |
| | |