 REVIEW COMMENTS - FIRE
  
 COVER SHEET
 DESIGN SHALL CONFORM TO THE FLORIDA FIRE PREVENTION
 CODE 2007 EDITION (NFPA 1 AND NFPA 101 - 2006 EDITION
 WITH FLORIDA AMENDMENTS).
  
 SHEET A-001
 THE REFERENCES TO THE INTERNATIONAL BUILDING CODE DO
 NOT APPLY TO THIS PROJECT.
  
 COMMON PATH OF TRAVEL AND EXIT ACCESS DISTANCES SHALL
 COMPLY WITH DISTANCES LISTED IN THE FLORIDA FIRE
 PREVENTION CODE.
  
 FIRE-RATED WALLS NOT SHOWN ON PLAN.
  
 EXIT SIGNAGE NOT SHOWN ON LIFE SAFETY PLAN.
  
 PROVIDE TACTILE SIGNAGE AT EXITS.
  
 SHOW PROPOSED LOCATIONS OF PORTABLE FIRE EXTINGUISHERS.
 EXTINGUISHERS SHALL HAVE A MINIMUM RATING OF 2A:10BC.
  
 SHEET A-101
 DEMOLITION SHALL COMPLY WITH THE REQUIREMENTS OF NFPA
 241.
  
 SEPARATE PLANS AND PERMIT REQUIRED FOR FIRE SPRINKLER
 WORK.
  
 SHEET A-601
 EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE
 PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING
 FIRE/SMOKE BARRIER--PROTECT ALL OPENINGS. CHARACTERS
 SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN
 WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15
 FEET ON CENTER. (REFERENCE: SECTION 8.3.2.4 OF FLORIDA
 FIRE PREVENTION CODE ??? NFPA 101)
  
 SHEET A-602
 DOOR SCHEDULE REFERENCES DETAILS THAT DO NOT EXIST ON
 SHEET A-601.
  
 SHEET E-111
 DEMOLITION WORK (WALL REMOVAL) MAY AFFECT FIRE ALARM
 DEVICE LOCATIONS. SEPARATE PLANS AND PERMIT REQUIRED
 FOR FIRE ALARM WORK.
  
 SHEET E-112
 NO EMERGENCY LIGHTING SHOWN.
  
 SHEET FS-1
 SEPARATE PLANS AND PERMIT REQUIRED FOR KITCHEN HOOD
 SUPPRESSION SYSTEM MODIFICATION.
  
 WESLEY JOLIN
 WEST PALM BEACH FIRE RESCUE
 FIRE & LIFE SAFETY PLAN REVIEW
  