2010-12-27 14:22:22*****PROVISO*****
  
 404.11 PIPING UNDERGROUND BENEATH BUILDINGS.
 PIPING INSTALLED UNDERGROUND BENEATH BUILDINGS
 IS PROHIBITED EXCEPT WHERE THE PIPING IS
 ENCASED IN A CONDUIT OF WROUGHT IRON, PLASTIC
 PIPE, OR STEEL PIPE DESIGNED TO WITHSTAND THE
 SUPERIMPOSED LOADS. SUCH CONDUIT SHALL EXTEND
 INTO AN OCCUPIABLE PORTION OF THE BUILDING AND,
 AT THE POINT WHERE THE CONDUIT TERMINATES IN
 THE BUILDING, THE SPACE BETWEEN THE CONDUIT
 AND THE GAS PIPING SHALL BE SEALED TO PREVENT
 THE POSSIBLE ENTRANCE OF ANY GAS LEAKAGE.
 WHERE THE END SEALING IS CAPABLE OF
 WITHSTANDING THE FULL PRESSURE OF THE GAS PIPE,
 THE CONDUIT SHALL BE DESIGNED FOR THE SAME
 PRESSURE AS THE PIPE. SUCH CONDUIT SHALL EXTEND
 NOT LESS THAN 4 INCHES (102 MM) OUTSIDE THE
 BUILDING, SHALL BE VENTED ABOVE GRADE TO THE
 OUTDOORS, AND SHALL BE INSTALLED SO AS TO PREVENT
 THE ENTRANCE OF WATER AND INSECTS. THE CONDUIT
 SHALL BE PROTECTED FROM CORROSION IN ACCORDANCE
 WITH SECTION 404.8.
  
 PLUMBING PERMIT REQUIRED
 GAS PERMIT REQUIRED
  