| 2010-12-21 15:08:57 | MIJAS TEX MEX RESTAURANT | | | 10130 NORTHLAKE BOULEVARD, SUITE 102 | | | PERMIT NUMBER 10120447 | | | | | | | | | 1. ALL CONSTRUCTION, DEMOLITION, AND RENOVATION TO | | | COMPLY WITH NFPA 241. | | | | | | 2. SEPARATE PLANS AND PERMITS REQUIRED FOR NEW HOOD, | | | DUCT, AND FIRE SUPPRESSION SYSTEM. | | | | | | 3. TACTILE SIGNAGE REQUIRED AT EXIT DOOR LOCATIONS. | | | | | | 4. SEPARATE PLANS AND PERMITS REQUIRED FOR FIRE | | | SPRINKLER SYSTEM REMODEL. PLEASE ENSURE FIRE SPRINKLER | | | PROTECTION IN EXISTING WALK-IN COOLER. | | | | | | 5. NEW GAS LINE TO BE INSTALLED IN ACCORDANCE WITH | | | APPLICABLE STANDARDS AND IN A SAFE RELIABLE MANNER. | | | | | | 6. PLEASE ENSURE THAT ALL EXIT SIGNS AND EMERGENCY | | | LIGHTS ARE IN GOOD WORKING ORDER. | | | | | | 7. ON SEVERAL SHEETS THE BACKS OF THE SEATS APPEAR TOO | | | CLOSE TOGETHER IN EXISTING DINING AREA 103. | | | | | | 8. ALL EXIT DOORS SUBJECT TO AN OCCUPANCY LOAD OF 100 | | | OR MORE PERSONS SHALL BE EQUIPPED WITH PANIC HARDWARE. | | | | | | 9. IS THE EXISTING OUTDOOR DINING AREA 104 HAVE A ROOF | | | OR IS IT OPEN TO THE SKY? | | | | | | | | | DENIED | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|