| Plan Review Notes For Permit 10120443 |
| Permit Number |
10120443 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-12-17 15:29:24 | ***PROVISO** | | | | | | 1. PROVIDE DETAIL FOR INSTALLATION AND ATTACHMENT OF | | | NEW ROOF CURB TO STRUCTURE AND NEW EQUIPMENT TO CURB | | | PER FBC-M 301.12. | | | 2. PROVIDE WIND RESISTANCE DATA, PRODUCT APPROVAL OR | | | CERTIFICATION FROM STRUCTURAL ENGINEER REGARDIN WIND | | | RESISTANCE OF THE NEWLY INSTALLED EQUIPMENT PER FBC-M | | | 301.12. | | | 3. CLEARANCE UNDER NEW EQUIPMENT SHALL BE IN ACCORDANCE | | | WITH FBC-B TABLE 1509.7 | | | 4. NEW ELECTRICAL CIRCUIT REQUIRED FOR NEW CONDENSING | | | UNITS. SEPARATE ELECTRICAL PLANS AND PERMIT REQUIRED. | | | 5. PROVIDE INFORMATION ON INSULATION TO BE USED ON | | | SUPPLY DUCT IN SHAFT PER FBC-M 604.1. | | | | | | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT: | | | RONALD J. REGUEIRO | | | 561.805.6719 | | | [email protected] |
|