2010-12-17 15:29:24***PROVISO**
  
 1. PROVIDE DETAIL FOR INSTALLATION AND ATTACHMENT OF
 NEW ROOF CURB TO STRUCTURE AND NEW EQUIPMENT TO CURB
 PER FBC-M 301.12.
 2. PROVIDE WIND RESISTANCE DATA, PRODUCT APPROVAL OR
 CERTIFICATION FROM STRUCTURAL ENGINEER REGARDIN WIND
 RESISTANCE OF THE NEWLY INSTALLED EQUIPMENT PER FBC-M
 301.12.
 3. CLEARANCE UNDER NEW EQUIPMENT SHALL BE IN ACCORDANCE
 WITH FBC-B TABLE 1509.7
 4. NEW ELECTRICAL CIRCUIT REQUIRED FOR NEW CONDENSING
 UNITS. SEPARATE ELECTRICAL PLANS AND PERMIT REQUIRED.
 5. PROVIDE INFORMATION ON INSULATION TO BE USED ON
 SUPPLY DUCT IN SHAFT PER FBC-M 604.1.
  