| Plan Review Notes For Permit 10120436 |
| Permit Number |
10120436 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-04 12:05:33 | PLANS DENIED | | | PLANS ARE NOT COMPLETE | | | PLEASE PROVIDE DUCT SIZE, EQUIPMENT SCHEDULE AND FRESH | | | AIR CALCULATIONS ON THE PLANS. | | | PLEASE INDICATE THE PURPOSE OF THE FUME EXTRACTION, IF | | | IT IS FOR A NAIL SALON THEN REFER TO TABLE 403.3 | | | REQUIRED OUTDOOR VENTILATION. | | | PLEASE SHOW ON THE PLANS HOW THE NEW R/T IS GETTING | | | BACK TO AHU # 1 & 2 | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 |
|