| 2011-01-11 08:07:27 | PROVIDE EMERGENCY EGRESS LIGHTING. FBC 1006 | | | PROVIDE AUTOMATIC LIGHTING CONTROL. FBC 13-415ABC.1.2 | | | PROVIDE A PANEL SCHEDULE LISTING THE NUMBER OF | | | CIRCUITS, WIRE SIZE AND OVERCURRENT PROTECTION. NEC | | | 210.3 | | | PROVIDE A SIGN CIRCUIT. NEC 660.5 | | | PROVIDE AN INSTALLATION/MOUNTING DETAIL FOR THE FLOOR | | | RECEPTACLES. NEC 406.4 | | | | | | ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718 | | | |
|