| 2011-01-04 08:09:03 | BUILDING PLAN REVIEW |
| | PERMIT: 10120436/ 10010151 |
| | ADD: 771 VILLAGE BLVD# 204 |
| | CONT: GREY CONSTRUCTION |
| | TEL: (561)312-2766 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | REVIEW |
| | ACTION: DENIED |
| | |
| | |
| | 1 CRH DESIGN & DRAFTING IS WORKING OUT OF THE SCOPE OF |
| | THEIR LICENSE. PLEASE REVIEW |
| | FLORIDA STATUTE???S 481.229 ARCHITECTURE LICENSING LAWS |
| | AND EXEMPTIONS. CRH DESIGN |
| | & DRAFTING CAN NOT DESIGN FOR COMMERCIAL WORK, IF THEY |
| | SUBMIT ANY WORK TO THIS JURISDICTION IN THE FUTURE IT |
| | WILL BE TURNED OVER TO THE APPROPRIATE BOARD! |
| | |
| | 2) SHEET A-2 INDICATES ALL WORK IS EXISTING. PLEASE |
| | CORRECT, IT IS WORK THAT WAS COMPLETED WITHOUT BENEFIT |
| | OF PERMITS AND INSPECTIONS AS INDICATED BY LIST OF |
| | BUILDING CODE VIOLATIONS. |
| | |
| | 3) PLEASE CORRECT 2 EXISTING COFFER CEILING BY SEPARATE |
| | PERMIT (10120436), THIS WORK AND PROPOSED REVISION |
| | (10120436) IS ALL UNDER ONE PERMIT. THE REVISION NUMBER |
| | (10120436) IS FOR TRACKING PURPOSES ONLY. PLEASE NOTE |
| | THAT THE DROPPED COFFER CEILINGS NEVER INDICATED AS TO |
| | THE MINIMUM BUILDING TYPE AND WAS ISSUED WITH EITHER |
| | WHITE WOOD OR P.T. 2X4 FRAMING MEMBERS. PLEASE REVIEW |
| | SECTION FBC-B 603.1.1 AND THE USE OF COMBUSTIBLES- FIRE |
| | RETARDANT TREATED WOOD. PLEASE CORRECT ISSUED PLANS. |
| | |
| | 4) A-2 THE PROPOSED LEFT HALLWAY INDICATES A WIDTH OF |
| | 3???-7??? WITH 3???0??? DOORS THAT SWING INTO THE |
| | HALLWAY, PLEASE REVIEW SECTION FBC-B 1005.2 DOOR |
| | ENCROACHMENT. DOORS OPENING INTO THE PATH OF EGRESS |
| | TRAVEL SHALL NOT REDUCE THE REQUIRED WIDTH TO LESS THAN |
| | ONE-HALF DURING THE COURSE OF THE SWING. WHEN FULLY |
| | OPEN, THE DOOR SHALL NOT PROJECT MORE THAN 7 INCHES |
| | (178 MM) INTO THE REQUIRED WIDTH. THE MINIMUM WIDTH OF |
| | A CORRIDOR WITH AN OCCUPANT LOAD OF LESS THAN 50 WOULD |
| | BE 4???-6???. |
| | |
| | 5) A-2 THERE ARE OFFICES WITH DOORS AND GLAZING JUST |
| | ADJACENT TO THE DOORWAY PLEASE INDICATE COMPLIANCE WITH |
| | FBC-B 2406.3 HAZARDOUS LOCATIONS. THE FOLLOWING SHALL |
| | BE CONSIDERED SPECIFIC HAZARDOUS LOCATIONS REQUIRING |
| | SAFETY GLAZING MATERIALS: |
| | (6.) GLAZING IN AN INDIVIDUAL FIXED OR OPERABLE PANEL |
| | ADJACENT TO A DOOR WHERE THE NEAREST EXPOSED EDGE OF |
| | THE GLAZING IS WITHIN A 24-INCH (610 MM) ARC OF EITHER |
| | VERTICAL EDGE OF THE DOOR IN A CLOSED POSITION AND |
| | WHERE THE BOTTOM EXPOSED EDGE OF THE GLAZING IS LESS |
| | THAN 60 INCHES (1524 MM) ABOVE THE WALKING SURFACE. |
| | 6) A-2 PLANS ARE CIRCLED IN RED INK (3) LOCATIONS WHERE |
| | PLANS WILL NEED TO COMPLY WITH |
| | FBC-B 11-4.13.6 MANEUVERING CLEARENCES AT DOORS. |
| | MINIMUM MANEUVERING CLEARANCES AT DOORS THAT ARE NOT |
| | AUTOMATIC OR POWER-ASSISTED SHALL BE AS SHOWN IN FIG. |
| | 25. THE FLOOR OR GROUND AREA WITHIN THE REQUIRED |
| | CLEARANCES SHALL BE CLEAR & LEVEL. IN SWING DOORS |
| | REQUIRES 18??? CLEAR. |
| | |
| | 7) A-2 RECEIVING ROOM OR BREAK ROOM PLEASE PROVIDE |
| | DETAILS ON SINK: 11-4.24.2 HEIGHT. SINKS SHALL BE |
| | MOUNTED WITH THE COUNTER OR RIM NO HIGHER THAN 34" |
| | ABOVE THE FINISH FLOOR. |
| | 11-4.24.3 KNEE CLEARANCE THAT IS AT LEAST 27" HIGH 30" |
| | WIDE, AND 19" DEEP SHALL BE PROVIDED UNDERNEATH SINKS. |
| | 11-4.24.5 CLEAR FLOOR SPACE. A CLEAR FLOOR SPACE AT |
| | LEAST 30 INCHES BY 48 INCHES (760 MM BY 1219 MM) |
| | COMPLYING WITH SECTION 11-4.2.4 SHALL BE PROVIDED IN |
| | FRONT OF A SINK TO ALLOW FORWARD APPROACH. THE CLEAR |
| | FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| | EXTEND A MAXIMUM OF 19 INCHES (485 MM) UNDERNEATH THE |
| | SINK. |
| | |
| | 8) A-2 FRONT COUNTER PLEASE SHOW COMPLIANCE WITH: |
| | 11-7.2 SALES AND SERVICE COUNTERS, TELLER WINDOWS, |
| | INFORMATION COUNTERS. |
| | (1) IN DEPARTMENT STORES AND MISCELLANEOUS RETAIL |
| | STORES WHERE COUNTERS HAVE CASH REGISTERS AND ARE |
| | PROVIDED FOR SALES OR DISTRIBUTION OF GOODS OR SERVICES |
| | TO THE PUBLIC, AT LEAST ONE OF EACH TYPE SHALL HAVE A |
| | PORTION OF THE COUNTER WHICH IS AT LEAST 36 INCHES (915 |
| | MM) IN LENGTH WITH A MAXIMUM HEIGHT OF 36 INCHES (915 |
| | MM) ABOVE THE FINISH FLOOR. IT SHALL BE ON AN |
| | ACCESSIBLE ROUTE COMPLYING WITH SECTION 11-4.3. THE |
| | ACCESSIBLE COUNTERS MUST BE DISPERSED THROUGHOUT THE |
| | BUILDING OR FACILITY. IN ALTERATIONS WHERE IT IS |
| | TECHNICALLY INFEASIBLE TO PROVIDE AN ACCESSIBLE |
| | COUNTER, AN AUXILIARY COUNTER MEETING THESE |
| | REQUIREMENTS MAY BE PROVIDED. |
| | |
| | (2) AT TICKETING COUNTERS, TELLER STATIONS IN A BANK, |
| | REGISTRATION COUNTERS IN HOTELS AND MOTELS, BOX OFFICE |
| | TICKET COUNTERS, AND OTHER COUNTERS THAT MAY NOT HAVE A |
| | CASH REGISTER BUT AT WHICH GOODS OR SERVICES ARE SOLD |
| | OR DISTRIBUTED, EITHER: |
| | |
| | (I) A PORTION OF THE MAIN COUNTER WHICH IS A MINIMUM OF |
| | 36 INCHES (915 MM) IN LENGTH SHALL BE PROVIDED WITH A |
| | MAXIMUM HEIGHT OF 36 INCHES (915 MM); OR |
| | |
| | (II) AN AUXILIARY COUNTER WITH A MAXIMUM HEIGHT OF 36 |
| | IN (915 MM) IN CLOSE PROXIMITY TO THE MAIN COUNTER |
| | SHALL BE PROVIDED; OR |
| | |
| | (III) EQUIVALENT FACILITATION SHALL BE PROVIDED (E.G., |
| | AT A HOTEL REGISTRATION COUNTER, EQUIVALENT |
| | FACILITATION MIGHT CONSIST OF: |
| | |
| | (1) PROVISION OF A FOLDING SHELF ATTACHED TO THE MAIN |
| | COUNTER ON WHICH AN INDIVIDUAL WITH DISABILITIES CAN |
| | WRITE, AND |
| | |
| | (2) USE OF THE SPACE ON THE SIDE OF THE COUNTER OR AT |
| | THE CONCIERGE DESK, FOR HANDING MATERIALS BACK AND |
| | FORTH). |
| | |
| | ALL ACCESSIBLE SALES AND SERVICE COUNTERS SHALL BE ON |
| | AN ACCESSIBLE ROUTE COMPLYING WITH SECTION 11-4.3. |
| | |
| | 9) 11-4.30.6SIGNAGE, ACCESSIBILITY, MOUNTING LOCATION |
| | AND HEIGHT. WHERE PERMANENT IDENTIFICATION IS PROVIDED |
| | FOR ROOMS AND SPACES, SIGNS SHALL BE INSTALLED ON THE |
| | WALL ADJACENT TO THE LATCH SIDE OF THE DOOR. WHERE |
| | THERE IS NO WALL SPACE TO THE LATCH SIDE OF THE DOOR, |
| | INCLUDING AT DOUBLE LEAF DOORS, SIGNS SHALL BE PLACED |
| | ON THE NEAREST ADJACENT WALL. MOUNTING HEIGHT SHALL BE |
| | 60 INCHES (1525 MM) ABOVE THE FINISH FLOOR TO THE |
| | CENTERLINE OF THE SIGN. MOUNTING LOCATION FOR SUCH |
| | SIGNAGE SHALL BE SO THAT A PERSON MAY APPROACH WITHIN 3 |
| | INCHES (76 MM) OF SIGNAGE WITHOUT ENCOUNTERING |
| | PROTRUDING OBJECTS OR STANDING WITHIN THE SWING OF A |
| | DOOR. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |