Plan Review Notes
Plan Review Notes For Permit 10120411
Permit Number 10120411
Review Stop B
Sequence Number 2
Notes
Date Text
2011-01-31 15:31:41RESIDENTIAL (R3) BUILDING REVIEW SECOND CHECKLIST.
 2007 FBC WITH 2009 REVISIONS.
  
 1- PROVIDE RECORDED NOTICE OF COMMENCEMENT. SEC. 713.13
 FLORIDA STATUTES.
 ***NOTE: THIS MAY BE RECORDED AT TIME OF PERMIT PICK
 UP.
  
 2- SPECIFY TYPE OF EXISTING WINDOWS TO BE REPLACED TO
 VERIFY COMPLIANCE WITH THE BEDROOM EGRESS REQUIREMENTS
 SEC. R310 2007 FLORIDA RESIDENTIAL CODE AND SEC. 601.2
 OF 2007 FBC-EXISTING. (REPEAT COMMENT. NOT ADDRESSED).
  
 3- SPECIFY ON PLANS SAFETY GLASS FOR WINDOWS #3, 5, 6
 AND 7 AS REQUIRED BY SEC. R308.4 OF 2007 FLORIDA
 RESIDENTIAL CODE.
  
 4- THERE IS A NEW PLUMBING PLAN PROVIDED. SCOPE OF WORK
 IS NOT LISTED ON THE SCOPE OF WORK "EXHIBIT 1". CLARIFY
 WHERE IS THIS NEW SINK GOING TO BE INSTALLED?. SEC.
 106.1.1 CITY AMENDMENTS TO FBC.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712