| 2011-02-24 15:03:08 | BUILDING PLAN REVIEW |
| | PERMIT: 10120395 |
| | ADD: 3031 OKEECHOBEE BLVD |
| | CONT: POPPER & ASSOCIATES |
| | TEL: (561)719-7136 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 2ND REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET A-100 PROVIDES THE CODE SUMMARY THE BUILDING |
| | TYPE INDICATES IT TO BE A TYPE II-B UNSPRINKLERED. |
| | PLEASE REVIEW THE CRITERIA FOR PLYWOOD SUB-SHEATHING. |
| | 2007 FBC-B 603.1.1 |
| | FIRE RETARDANT TREATED WOOD SHALL BE PERMITTED IN: |
| | 1.2 NONBEARING EXTERIOR WALLS WHERE NO FIRE RATING IS |
| | REQUIRED. |
| | |
| | 2) 2007 FBC-B SECTION 1407 DEALS WITH MCM OR METAL |
| | COMPOSITE MATERIALS. IN THIS CASE THE MINIMUM BUILDING |
| | YPE IS UNKNOWN AND WILL NEED TO BE IDENTIFIED BUT THERE |
| | ARE GENERAL CODE SECTIONS THAT WILL NEED FURTHER |
| | DOCUMENTATION FOR CODE COMPLIANCE: |
| | 2A) SUBMIT MANUFACTURES TESSTING FOR COMPONENTS AND |
| | CLADDING AND ASSOCIATED PRESSURES. |
| | 1407.4 STRUCTURAL DESIGN. MCM SYSTEMS SHALL BE DESIGNED |
| | AND CONSTRUCTED TO RESIST WIND LOADS AS REQUIRED BY |
| | CHAPTER 16 FOR COMPONENTS AND CLADDING. IN PART SOME OF |
| | THE MCM PANELS WILL BE CONSIDERED ARCHITECTURAL |
| | EMBELLISHMENTS AND IN PART SOME WILL BE CONSIDERED |
| | COMPONENTS AND CLADDING, IN EITHER CASE SHEET S-1 |
| | PROVIDES THE WIND DESIGN CRITERIA, BUT NOT THE POSITIVE |
| | AND NEGATIVE PRESSURES FOR THE INTERIOR ZONES AND END |
| | ZONES, PLEASE PROVIDE PRESSURES. |
| | |
| | |
| | 2B) 1407.5 APPROVAL. RESULTS OF APPROVED TESTS OR AN |
| | ENGINEERING ANALYSIS SHALL BE SUBMITTED TO THE BUILDING |
| | OFFICIAL TO VERIFY COMPLIANCE WITH THE REQUIREMENTS OF |
| | CHAPTER 16 FOR WIND LOADS. SINCE THE WIND PRESSURES |
| | POSITIVE & NEGATIVE HAVE NOT BEEN PROVIDED AS REQUESTED |
| | THE TESTING REPORT SUBMITTED CAN NOT BE EVALUATED, IT |
| | DOES APPEAR THAT THE PRESSURES ARE LOW!!! |
| | |
| | 2C) 1407.6 WEATHER RESISTANCE. MCM SYSTEMS SHALL COMPLY |
| | WITH SECTION 1403 AND SHALL BE DESIGNED AND CONSTRUCTED |
| | TO RESIST WIND AND RAIN IN ACCORDANCE WITH THIS SECTION |
| | AND THE MANUFACTURER'S INSTALLATION INSTRUCTIONS. THE |
| | COMMEENTS AS FAR AS AN ARCHITECTURAL EMBELISHMENT IN |
| | PART YES, IN PART THEY WILL NEED TO BE THOUGHT AS |
| | COMPONENTS AND CLADDING , IN EITHER CASE THE PANELS |
| | WILL NEED TO BE EVALUATED FOR WIND AND THE POSITIVE AND |
| | NEGATIVE PRESSURES FOR INTERIOR ZONES AND END ZONES. |
| | |
| | 2D) 1407.7 DURABILITY. MCM SYSTEMS SHALL BE CONSTRUCTED |
| | OF APPROVED MATERIALS THAT MAINTAIN THE PERFORMANCE |
| | CHARACTERISTICS REQUIRED IN SECTION 1407 FOR THE |
| | DURATION OF USE. |
| | |
| | 3) 1407.9 SURFACE-BURNING CHARACTERISTICS. UNLESS |
| | OTHERWISE SPECIFIED, MCM SHALL HAVE A FLAME SPREAD |
| | INDEX OF 75 OR LESS AND A SMOKE-DEVELOPED INDEX OF 450 |
| | OR LESS WHEN TESTED AS AN ASSEMBLY IN THE MAXIMUM |
| | THICKNESS INTENDED FOR USE IN ACCORDANCE WITH ASTM E |
| | 84. WITH PART OF MCM PANELS BEING CONSIDERED COMPONENTS |
| | AND CLADDING THIS CODE SECTION IS STILL AN ISSUE, |
| | PROVIDE PRODUCT TESTING. |
| | |
| | 4) 1407.10 TYPE I, II, III AND IV CONSTRUCTION. WHERE |
| | INSTALLED ON BUILDINGS OF TYPE I, II, III AND IV |
| | CONSTRUCTION, MCM SYSTEMS SHALL COMPLY WITH SECTIONS |
| | 1407.10.1 THROUGH 1407.10.4, OR 1407.11. |
| | TYPE II-B CONSTRUCTION DOES ALLOW FOR THE USE OF MCM |
| | PANELS THAT WILL NEED TO MET 603.1.2 EXCEPTION 10. |
| | |
| | 5) PLEASE PROVIDE COMPLIANCE. 1407.10.2 THERMAL |
| | BARRIERS. MCM SHALL BE SEPARATED FROM THE INTERIOR OF A |
| | BUILDING BY AN APPROVED THERMAL BARRIER CONSISTING OF |
| | 0.5-INCH (12.7 MM) GYPSUM WALLBOARD OR EQUIVALENT |
| | THERMAL BARRIER MATERIAL THAT WILL LIMIT THE AVERAGE |
| | TEMPERATURE RISE OF THE UNEXPOSED SURFACE TO NOT MORE |
| | THAN 250DEGRESSF (121DEGRESSC) AFTER 15 MINUTES OF FIRE |
| | EXPOSURE IN ACCORDANCE WITH THE STANDARD |
| | TIME-TEMPERATURE CURVE OF ASTM E 119. THE THERMAL |
| | BARRIER SHALL BE INSTALLED IN SUCH A MANNER THAT IT |
| | WILL REMAIN IN PLACE FOR NOT LESS THAN 15 MINUTES BASED |
| | ON A TEST CONDUCTED IN ACCORDANCE WITH UL 1715. |
| | |
| | 1407.10.3 THERMAL BARRIER NOT REQUIRED. THE THERMAL |
| | BARRIER SPECIFIED FOR MCM IN SECTION 1407.10.2 IS NOT |
| | REQUIRED WHERE: |
| | |
| | 1. THE MCM SYSTEM IS SPECIFICALLY APPROVED BASED ON |
| | TESTS CONDUCTED IN ACCORDANCE WITH UL 1040 OR UL 1715. |
| | SUCH TESTING SHALL BE PERFORMED WITH THE MCM IN THE |
| | MAXIMUM THICKNESS INTENDED FOR USE. THE MCM SYSTEM |
| | SHALL INCLUDE SEAMS, JOINTS AND OTHER TYPICAL DETAILS |
| | USED IN THE INSTALLATION AND SHALL BE TESTED IN THE |
| | MANNER INTENDED FOR USE. |
| | |
| | 6) COMPLIED. |
| | |
| | |
| | 7) COMPLIED. |
| | |
| | 8) PROVISO: |
| | 1407.13 LABELING. MCM SHALL BE LABELED IN ACCORDANCE |
| | WITH SECTION 1703.5. |
| | 1703.5 LABELING. WHERE MATERIALS OR ASSEMBLIES ARE |
| | REQUIRED BY THIS CODE TO BE LABELED, SUCH MATERIALS AND |
| | ASSEMBLIES SHALL BE LABELED BY AN APPROVED AGENCY IN |
| | ACCORDANCE WITH SECTION 1703. PRODUCTS AND MATERIALS |
| | REQUIRED TO BE LABELED SHALL BE LABELED IN ACCORDANCE |
| | WITH THE PROCEDURES SET FORTH IN SECTIONS 1703.5.1 |
| | THROUGH 1703.5.3. |
| | |
| | 1703.5.1 TESTING. AN APPROVED AGENCY SHALL TEST A |
| | REPRESENTATIVE SAMPLE OF THE PRODUCT OR MATERIAL BEING |
| | LABELED TO THE RELEVANT STANDARD OR STANDARDS. THE |
| | APPROVED AGENCY SHALL MAINTAIN A RECORD OF THE TESTS |
| | PERFORMED. THE RECORD SHALL PROVIDE SUFFICIENT DETAIL |
| | TO VERIFY COMPLIANCE WITH THE TEST STANDARD. |
| | |
| | 1703.5.2 INSPECTION AND IDENTIFICATION. THE APPROVED |
| | AGENCY SHALL PERIODICALLY PERFORM AN INSPECTION, WHICH |
| | SHALL BE IN-PLANT IF NECESSARY, OF THE PRODUCT OR |
| | MATERIAL THAT IS TO BE LABELED. THE INSPECTION SHALL |
| | VERIFY THAT THE LABELED PRODUCT OR MATERIAL IS |
| | REPRESENTATIVE OF THE PRODUCT OR MATERIAL TESTED. |
| | |
| | 1703.5.3 LABEL INFORMATION. THE LABEL SHALL CONTAIN THE |
| | MANUFACTURER'S OR DISTRIBUTOR'S IDENTIFICATION, MODEL |
| | NUMBER, SERIAL NUMBER OR DEFINITIVE INFORMATION |
| | DESCRIBING THE PRODUCT OR MATERIAL'S PERFORMANCE |
| | CHARACTERISTICS AND APPROVED AGENCY'S IDENTIFICATION. |