Plan Review Notes
Plan Review Notes For Permit 10120377
Permit Number 10120377
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-12-20 15:43:1712/20/10 WHEN ANY SMOKE OR HEAT DETECTOR/MANUAL PULL
 STATION, SPRINKLER WATER FLOW SWITCH GOES INTO ALARM,
 IT WILL ACTIVATE THE FOLLOWING:
  
 1)A GENERAL FIRE ALARM.
  
 2)ALL FIRE ALARM HORN/STROBES & BELLS.
  
 3)ALARM CONTACTS WILL NOTIFY REMOTE MONITOR OF ALARM
 CONDITION.
  
 PLAN APPROVED
  
 PLAN REVIEWED BY CAPTAIN DANIELS
 WEST PALM BEACH FIRE RESCUE
 LIFE & SAFETY PLAN REVIEW
 561 805-6722
  