| Plan Review Notes For Permit 10120362 |
| Permit Number |
10120362 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-05 13:48:32 | LIST THE NUMBER OF CONDUCTORS INCLUDING THE NEUTRAL AND | | | EQUIPMENT BONDING (GROUND) CONDUCTOR SIZES FEEDING THE | | | 60 AMP PANEL. SPECIFY THE GROUNDING ELECTRODE TO BE | | | USED. NEC 250.32 (A) AND (B), TABLE 250.122 | | | SPECIFY THE TYPE OF CONDUIT TO BE UTILIZED AND THE NEMA | | | CLASSIFICATION FOR THE OUTSIDE DISCONNECT. NEC 110.11 | | | PROVIDE A PANEL SCHEDULE LISTING THE NUMBER OF | | | CIRCUITS, WIRE SIZE AND OVERCURRENT PROTECTION. NEC | | | 210.3 | | | NOTE ON THE PLAN THE REQUIREMENT FOR TAMPER RESISTANT | | | RECEPTACLES IN RESIDENTIAL OCCUPANCIES. NEC 406.11 | | | | | | ROBERT LECKY, ELECTRICAL PLANS REVIEW, 561-805-6718 |
|