| 2010-12-28 14:48:05 | 600 SOUTH ROSEMARY AVENUE, SUITE #140 | | | PERMIT #10120343 | | | REVIEW COMMENTS - FIRE | | | | | | GENERAL | | | BROWARD COUNTY IS REFERENCED IN THE TITLEBLOCK. | | | | | | ALL DEMOLITION WORK TO CONFORM TO THE REQUIREMENTS OF | | | NFPA 241. | | | | | | LOCATE PORTABLE FIRE EXTINGUISHER ALONG PATH OF EGRESS. | | | FIRE EXTINGUISHERS SHALL BE TAGGED BY A LICENSED FIRE | | | EQUIPMENT CONTRACTOR. MINIMUM RATING OF EXTINGUISHERS | | | SHALL BE 2A:10BC. | | | | | | SEPARATE PLANS AND PERMITS REQUIRED FOR ANY FIRE ALARM | | | OR FIRE SPRINKLER WORK. | | | | | | SHEET E2.0 | | | THE EXISTING FIRE ALARM NOTIFICATION APPLIANCES DO NOT | | | APPEAR TO COVER THE NORTH AREA OF THE SPACE. | | | | | | SHEET E3.0 | | | EXIT SIGN REQUIRED OVER DOUBLE EXIT DOORS LOCATED TO | | | THE SOUTH. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | | | | | | | |
|