2011-02-09 17:02:224215 UP THE GROVE LANE
 FLORIDA POWER AND LIGHT COMMAND BUILDING
 PERMIT NUMBER 10120325
  
 1. ON SHEET A-101 TWO FIRE DEPARTMENT CONNECTIONS ARE
 SHOWN. ONLY ONE IS REQUIRED TO SUPPORT THE FIRE
 SPRINKLER SYSTEM.
  
 2. THE EVACUATION MESSAGE ON FA2.01 NEEDS A SLIGHT
 CHANGE. PLEASE CHANGE THE WORD FROM FIRE TO EMERGENCY.
  
 3. KNOX LOCKING CAPS ARE REQUIRED FOR THE FIRE
 DEPARTMENT CONNECTION SHOWN ON FS2.01.
  
 4. THE INSTALLATION OF CARD READERS SHALL NOT INTERFERE
 WITH EXITING.
  
  
 APPROVED PROVISO
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION