| Plan Review Notes For Permit 10120325 |
| Permit Number |
10120325 |
|
| Review Stop |
FIRE |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2011-02-09 17:02:22 | 4215 UP THE GROVE LANE | | | FLORIDA POWER AND LIGHT COMMAND BUILDING | | | PERMIT NUMBER 10120325 | | | | | | 1. ON SHEET A-101 TWO FIRE DEPARTMENT CONNECTIONS ARE | | | SHOWN. ONLY ONE IS REQUIRED TO SUPPORT THE FIRE | | | SPRINKLER SYSTEM. | | | | | | 2. THE EVACUATION MESSAGE ON FA2.01 NEEDS A SLIGHT | | | CHANGE. PLEASE CHANGE THE WORD FROM FIRE TO EMERGENCY. | | | | | | 3. KNOX LOCKING CAPS ARE REQUIRED FOR THE FIRE | | | DEPARTMENT CONNECTION SHOWN ON FS2.01. | | | | | | 4. THE INSTALLATION OF CARD READERS SHALL NOT INTERFERE | | | WITH EXITING. | | | | | | | | | APPROVED PROVISO | | | | | | | | | MIKE CARSILLO, BATTALION CHIEF | | | BUREAU OF FIRE PREVENTION |
|