| 2010-12-20 16:36:14 | FLORIDA POWER AND LIGHT GENERAL OFFICE AND COMMAND |
| | CENTER |
| | 4215 UP THE GROVE LANE |
| | PERMIT NUMBER 10120325 |
| | |
| | |
| | 1. SEPARATE PLANS AND PERMIT REQUIRED FOR FIRE ALARM |
| | AND FIRE SPRINKLER INSTALLATIONS. |
| | |
| | 2. WORKROOMS 110 AND 121 CANNOT BE LOCKED AS THEY SERVE |
| | AS EXIT ACCESS TO TWO EXIT DOORS. |
| | |
| | 3. ALL EXIT DOORS APPEAR TO BE PROVIDED WITH PANIC |
| | HARDWARE. CARE READERS SHALL NOT INTERFERE WITH ANY |
| | EXITING FROM THESE DOORS. |
| | |
| | 4. KNOX-BOX AND FIRE DEPARTMENT CONNECTION KNOX LOCKING |
| | CAPS CAN BE ORDERED AT WWW.KNOXBOX.COM. |
| | |
| | 5. ON SHEET LS-OOO SEVERAL CODE REFERENCES ARE LISTED |
| | THAT ARE NOT APPLICABLE TO THIS PROJECT, THEY INCLUDE |
| | NFPA 14, 45 AND 96. NFPA 241 SHOULD BE ADDED TO THE |
| | PLANS. |
| | |
| | 6. TACTILE SIGNAGE LOCATIONS SHOULD BE DISPLAYED ON |
| | LS-201. |
| | |
| | 7. PLEASE INDICATE PHYSICALLY CHALLENGED SEATING ON |
| | SHEET LS-201 WITHIN THE COMMAND CENTER. |
| | |
| | 8. THE REQUIRED FIRE ALARM SYSTEM IS TO BE THIRD PARTY |
| | MONITORED BY A LICENSED CENTRAL STATION APPROVED FOR |
| | CENTRAL STATION SERVICE. |
| | |
| | 9. THE FIRE ALARM SYSTEM SHALL BE PROVIDED WITH VOICE |
| | EVACUATION. PLEASE INDICATE WHAT THE VOICE EVACUATION |
| | MESSAGE WILL INDICATE. |
| | |
| | 10. SEPARATE PLANS AND PERMITS REQUIRED FOR THE |
| | EMERGENCY GENERATOR. |
| | |
| | 11. ON SHEET FA1.01 HORN STROBES ARE SHOWN. THESE |
| | SHOULD BE SPEAKER STROBES. |
| | |
| | 12. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT |
| | LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS. |
| | |
| | 13. WORKROOMS 110 AND 121 DO NOT APPEAR TO CONTAIN ANY |
| | EMERGENCY LIGHTING EQUIPMENT ON SHEET E2.01. |
| | |
| | 14. EXIT SIGNS NOT SHOWN ON SHEET E2.01. |
| | |
| | 15. ON SHEET A101 DISCREPANCIES EXIST RELATED TO THE |
| | FIRE SAFETY EQUIPMENT THAT ARE DISPLAYED ON THE CIVIL |
| | DRAWINGS. |
| | |
| | 16. ON SHEET A101 THE "EMERGENCY VEHICLE ACCESS WITH |
| | HARDENED SUB-BASE " IF EXPECTED TO SUPPORT FIRE |
| | EQUIPMENT MUST BE CONSTRUCTED TO SUPPORT 32 TONS. |
| | |
| | 17. ON SHEET A-501 THE BUILDING ADDRESS IS NOT SHOWN ON |
| | ANY ELEVATION DRAWINGS. THE BUILDING ADDRESS IS TO BE A |
| | MINIMUM OF 6" HIGH AND AT LEAST 1" WIDE. |
| | |
| | 18. THE LOCATION OF THE BACKFLOW DEVICE ON SHEET FS1-01 |
| | DOES NOT APPEAR TO CORRESPOND TO THE CIVIL SHEETS. |
| | |
| | 19. IN THE SCOPE OF WORK SECTION ON SHEET FS-201 IT |
| | INDICATES A THREE STORY BUILDING. THE BUILDING IS ONLY |
| | ONE STORY. |
| | |
| | |
| | DENIED |
| | |
| | |
| | MIKE CARSILLO, BATTALION CHIEF |
| | BUREAU OF FIRE PREVENTION |
| | |