Plan Review Notes
Plan Review Notes For Permit 10120325
Permit Number 10120325
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2010-12-20 16:36:14FLORIDA POWER AND LIGHT GENERAL OFFICE AND COMMAND
 CENTER
 4215 UP THE GROVE LANE
 PERMIT NUMBER 10120325
  
  
 1. SEPARATE PLANS AND PERMIT REQUIRED FOR FIRE ALARM
 AND FIRE SPRINKLER INSTALLATIONS.
  
 2. WORKROOMS 110 AND 121 CANNOT BE LOCKED AS THEY SERVE
 AS EXIT ACCESS TO TWO EXIT DOORS.
  
 3. ALL EXIT DOORS APPEAR TO BE PROVIDED WITH PANIC
 HARDWARE. CARE READERS SHALL NOT INTERFERE WITH ANY
 EXITING FROM THESE DOORS.
  
 4. KNOX-BOX AND FIRE DEPARTMENT CONNECTION KNOX LOCKING
 CAPS CAN BE ORDERED AT WWW.KNOXBOX.COM.
  
 5. ON SHEET LS-OOO SEVERAL CODE REFERENCES ARE LISTED
 THAT ARE NOT APPLICABLE TO THIS PROJECT, THEY INCLUDE
 NFPA 14, 45 AND 96. NFPA 241 SHOULD BE ADDED TO THE
 PLANS.
  
 6. TACTILE SIGNAGE LOCATIONS SHOULD BE DISPLAYED ON
 LS-201.
  
 7. PLEASE INDICATE PHYSICALLY CHALLENGED SEATING ON
 SHEET LS-201 WITHIN THE COMMAND CENTER.
  
 8. THE REQUIRED FIRE ALARM SYSTEM IS TO BE THIRD PARTY
 MONITORED BY A LICENSED CENTRAL STATION APPROVED FOR
 CENTRAL STATION SERVICE.
  
 9. THE FIRE ALARM SYSTEM SHALL BE PROVIDED WITH VOICE
 EVACUATION. PLEASE INDICATE WHAT THE VOICE EVACUATION
 MESSAGE WILL INDICATE.
  
 10. SEPARATE PLANS AND PERMITS REQUIRED FOR THE
 EMERGENCY GENERATOR.
  
 11. ON SHEET FA1.01 HORN STROBES ARE SHOWN. THESE
 SHOULD BE SPEAKER STROBES.
  
 12. SMOKE DETECTORS SHALL BE INSTALLED A MINIMUM OF AT
 LEAST THREE FEET FROM AIR CONDITIONER DIFFUSERS.
  
 13. WORKROOMS 110 AND 121 DO NOT APPEAR TO CONTAIN ANY
 EMERGENCY LIGHTING EQUIPMENT ON SHEET E2.01.
  
 14. EXIT SIGNS NOT SHOWN ON SHEET E2.01.
  
 15. ON SHEET A101 DISCREPANCIES EXIST RELATED TO THE
 FIRE SAFETY EQUIPMENT THAT ARE DISPLAYED ON THE CIVIL
 DRAWINGS.
  
 16. ON SHEET A101 THE "EMERGENCY VEHICLE ACCESS WITH
 HARDENED SUB-BASE " IF EXPECTED TO SUPPORT FIRE
 EQUIPMENT MUST BE CONSTRUCTED TO SUPPORT 32 TONS.
  
 17. ON SHEET A-501 THE BUILDING ADDRESS IS NOT SHOWN ON
 ANY ELEVATION DRAWINGS. THE BUILDING ADDRESS IS TO BE A
 MINIMUM OF 6" HIGH AND AT LEAST 1" WIDE.
  
 18. THE LOCATION OF THE BACKFLOW DEVICE ON SHEET FS1-01
 DOES NOT APPEAR TO CORRESPOND TO THE CIVIL SHEETS.
  
 19. IN THE SCOPE OF WORK SECTION ON SHEET FS-201 IT
 INDICATES A THREE STORY BUILDING. THE BUILDING IS ONLY
 ONE STORY.
  
  
 DENIED
  
  
 MIKE CARSILLO, BATTALION CHIEF
 BUREAU OF FIRE PREVENTION
  