Plan Review Notes
Plan Review Notes For Permit 10120325
Permit Number 10120325
Review Stop B
Sequence Number 1
Notes
Date Text
2010-12-29 15:52:41PERMIT: 10120325
 ADD: 4215 UP THE GROVE LN.
 CONT: ROYAL CONCRETE CONCEPTS
 TEL: (561)689-5395
  
 FL BLD CODE= 2007 FLORIDA BUILDING CODE
 W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 1ST REVIEW
 ACTION: DENIED
  
 1)THIS JOB WILL NOT REQUIRE NEITHER A THRESHOLD OR
 RESIDENT INSPECTOR BUT WILL NEED THE CONTRACTOR OF
 RECORD TO CONTACT CHIEF BUILDING INSPECTOR KEN CONRAD
 IN REGARDS TO ALL INSPECTIONS FOR JOB SITE WELDING,
 QUALIFICATIONS FOR JOB SITE WELDERS & CERTIFICATES.
 KEN CONRAD- TELEPHONE NUMBER (561) 805-6666.
  
 2) PLEASE PROVIDE 2 ORIGINAL SOILS TEST REPORTS SIGNED
 & SEALED. 1802.2.1 QUESTIONABLE SOIL. WHERE THE
 SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE
 A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS
 CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE
 THAT THE NECESSARY INVESTIGATION BE MADE. SUCH
 INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF
 SECTIONS 1802.4 THROUGH 1802.6 .
  
 3) THIS BUILDING IS LOCATED WITHIN A "A-8" FLLOOD ZONE.
 THE BASE ELEVATION IS TO BE AT 15'-0" PLUS AN ADDTIONAL
 6" A REQUIRED BY THE CITY CODE OF ORDINANCES SECTION
 94-546. THE FIRST FLOOR SLAB OF THE BUILDING IS
 ELEVATED ABOVE THE MINIMUM 15'-6" BUT THE GENERATOR
 SLAB ELEVATION IS NOT PROVIDED ON C3.1. PLEASE NOTE
 THAT NON-RESIDENTIAL CAN BE SET BELOW THIS HEIGHT BUT
 WOULD NEED TO
 DEMONSTRATE HOW THIS AREA WOULD BE FLOOD PROOFED.
  
 4) SHEET LS-000 INDICATES THIS BUILDING TO BE AN "A"
 ASSEMBLY OCCUPANCY WITHOUT PROVIDING A SUB GROUP A-1-
 A-5. THIS BUILDING BEING FPLCOMMAND CENTER IS TRUELY A
 BUSINESS OCCUPANCY, FBC-B 304.1 BUSINESS GROUP B.
 BUSINESS GROUP B OCCUPANCY INCLUDES, AMONG OTHERS, THE
 USE OF A BUILDING OR STRUCTURE, OR A PORTION THEREOF,
 FOR OFFICE, PROFESSIONAL OR SERVICE-TYPE TRANSACTIONS,
 INCLUDING STORAGE OF RECORDS AND ACCOUNTS.
  
 5) ADDITIONAL INFORMATION REQUIRED 106.1.2, DISCREPANCY
 IN THE PLANS. LS-201 EXIT DOORSINDICATE A 33 INCH WIDE
 DOOR, NOT CLEAR SPACE, THEN NEXT TO THIS STATEMENT THE
 GRAPHICS INDICATE A 34 INCH WIDE REQUIRED. A-201 DOORS
 110 & 121 INDICATE THEY ARE
 3'X7' ON THE DOOR SCHEDULE SHEET A-801.
  
 6) A-501 & A-801 THE PLANS INDICATE WHAT PRODUCT
 APPROVALS WILL BE INSTALLED ON THE JOBSITE BUT THE
 WHOLE APPROVAL HA NOT BEEN PROVIDED. BEFORE PERMIT
 ISSUANCE THEY WILL NEED TO BE PROVIDED FOR REVIEW.
 PLEASE NOTE ON MANY WINDOW AND DOOR APPROVALS THERE ARE
 MORE THAN ONE TYPE GLAZING SYSTEM THAT IS PART OF THE
 APPROVAL. PLEASE CIRCLE WHICH GLAZED SYSTEM WILL BE
 INSTALLED SINCE EFFECTS THE ASSOCIATED PRESSURES. RULE
 9N-3 (FORMERELY RULE 9B-72).
  
 FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2
 COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE
 AS FOLLOWS:
 6A) IMPACT WINDOWS- STOREFRONT
 6B) IMPACT WINDOWS- SPANDREL (SHEET A-501)
 6C) GLAZED EXTERIOR DOORS
 6D) METAL EXTERIOR DOORS
 6E) EXTERIOR LOUVERS
 6F) ROOFING ASSEMBLIES- NO APPROVAL INFORMATION WAS
 SUBMITTED. PLEASE NOTE THERE MAY BE SEPERATE SUBSYSTEMS
 LISTED WITHIN THE PRODUCT APPROVAL REPORT, HIGHLIGHT
 THE INTENDED SUB-SYSTEM AND NOTE THE ASSOCIATED
 PRESSURES AND IF ENHANCED FASTENING IS LISTED OR IS
 THERE A SYSTEM LIMITATION ON THAT SUB-SYSTEM.
  
 7) SHEET F-1 THE WIND DESIGN IS FIGURED AT 191 MPH
 WHICH IS HIGH, BUT THE BUILDING CATEGORY IS NOT A I BUT
 A LV. POWER GENERATING STATIONS AND OTHER PUBLIC
 UTILITIES FACILITIES REQUIRED IN AN EMERGENCY. THE
 IMPORTANCE FACTOR WILL CHANGE FROM A 1.0 TO A 1.15.
 THIS WILL CHANGE THE PRESSURES INDICATED ON THE PLANS
 AND POSSIBLY THE PROPOSED PRODUCT APPROVALS..
  
 8) SHEET F2 FLOOR SLABS PLEASE PROVIDE COMPLIANCE WITH
 1816.1 TERMITE PROTECTION / 1910.1. NOTED THIS CODE
 SECTION DEALS WITH
 SLABS ON GROUND, THE FOAM MAY ACT AS A PARTIAL BARRIER
 BUT THE BEAM PORTION OF THE FLOOR SLAB WILL EITHER BE
 IN DIRECT CONTACT WITH EARTH OR DIRECTLY ABOVE THE
 EARTH, ALOWING MOISTURE, CONDENSATION TO ENTER THE
 CONCERTE BEAM PORTION OF THE FLOOR SYSTEM AND SPAWLLING
 WOULD OCCUR OVER A PERIOD OF TIME. ALSO APPENDIX E302.1
 RADON GASSES.
  
 9) THE SECOND ISSUE WITH FOAM INSULATION IS SHEET A-601
 & A-651:
 9A) INTERIOR WALLS, PLEASE PROVIDE SURFACE- BURNING
 CHARACTERISTICS FOR THE FOAM USED WITHIN THE POURED
 WALLS. FBC-B 2603.3
 9B) THE PLANS INDICATE THE INTERIOR WALLS TO BE GWB,
 GYPSUM WALL BOARD BUT NO THICKNESS INDICATED, PLEASE
 REVIEW SECTION
 FBC-B 2603.4.
 9C) IN DETAIL # 2 THE UPPER PORTION OF WALL HAS NO
 INSULATION WITH IN THE WALL DOES THIS MEET WITH THE
 ENERGY CALCULATIONS?
 9D) IN DETAIL # 2 THE CENTRAL CORE, THE CEILING
 INDICATES EXPOSED TO THE ROOF DECK BELOW WHICH WOULD
 ALLOW FOR EXPOSED FOAM INSULATION, FBC-B 2603.4.
 9E) THIS SAME CONDITION EXIST IN THE MECHANICAL/
 ELECTRICAL ROOM# 114 AND THE SERVER ROOM # 115.
 9F) IN MANY OF THE OTHER ROOMS THE FINISH SCHEDULE
 INDICATES THE USE OF DROPPED CEILINGS, PLEASE INDICATE
 HOW THE THERMAL BARRIER WILL BE MAINTAINED.
  
 10) SHEET A-601/ A-651 DETAIL# 3, GUTTERS AND DOWN
 SPOUTS, PLEASE PROVIDE THE SCHEDULE( THICKNESS) FOR THE
 PVC DOWNSPOUTS PER
 FBC-B 1503.4.1.
  
 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT
 FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL
 PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND
 A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT
 APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY.
 A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW
 COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE
 THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR
 PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION.
  
 JAMES A. WITMER C.B.O.
 COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: (561)805-6715
 FAX:(561)805-6731
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP
  
 PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS
 LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS
 REGARDING CITY BUSINESS ARE PUBLIC RECORD, AVAILABLE TO
 THE PUBLIC UPON REQUEST. YOUR E-MAIL COMMUNICATIONS ARE
 THEREFORE SUBJECT TO PUBLIC DISCLOSURE.
  
 MEMBER OF BOAF: BUILDING OFFICIALS ASSOCIATION OF
 FLORIDA SAVING LIVES AND PROPERTY SINCE 1953
  
  
  
  
  