| 2010-12-29 15:52:41 | PERMIT: 10120325 |
| | ADD: 4215 UP THE GROVE LN. |
| | CONT: ROYAL CONCRETE CONCEPTS |
| | TEL: (561)689-5395 |
| | |
| | FL BLD CODE= 2007 FLORIDA BUILDING CODE |
| | W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1)THIS JOB WILL NOT REQUIRE NEITHER A THRESHOLD OR |
| | RESIDENT INSPECTOR BUT WILL NEED THE CONTRACTOR OF |
| | RECORD TO CONTACT CHIEF BUILDING INSPECTOR KEN CONRAD |
| | IN REGARDS TO ALL INSPECTIONS FOR JOB SITE WELDING, |
| | QUALIFICATIONS FOR JOB SITE WELDERS & CERTIFICATES. |
| | KEN CONRAD- TELEPHONE NUMBER (561) 805-6666. |
| | |
| | 2) PLEASE PROVIDE 2 ORIGINAL SOILS TEST REPORTS SIGNED |
| | & SEALED. 1802.2.1 QUESTIONABLE SOIL. WHERE THE |
| | SAFE-SUSTAINING POWER OF THE SOIL IS IN DOUBT, OR WHERE |
| | A LOAD-BEARING VALUE SUPERIOR TO THAT SPECIFIED IN THIS |
| | CODE IS CLAIMED, THE BUILDING OFFICIAL SHALL REQUIRE |
| | THAT THE NECESSARY INVESTIGATION BE MADE. SUCH |
| | INVESTIGATION SHALL COMPLY WITH THE PROVISIONS OF |
| | SECTIONS 1802.4 THROUGH 1802.6 . |
| | |
| | 3) THIS BUILDING IS LOCATED WITHIN A "A-8" FLLOOD ZONE. |
| | THE BASE ELEVATION IS TO BE AT 15'-0" PLUS AN ADDTIONAL |
| | 6" A REQUIRED BY THE CITY CODE OF ORDINANCES SECTION |
| | 94-546. THE FIRST FLOOR SLAB OF THE BUILDING IS |
| | ELEVATED ABOVE THE MINIMUM 15'-6" BUT THE GENERATOR |
| | SLAB ELEVATION IS NOT PROVIDED ON C3.1. PLEASE NOTE |
| | THAT NON-RESIDENTIAL CAN BE SET BELOW THIS HEIGHT BUT |
| | WOULD NEED TO |
| | DEMONSTRATE HOW THIS AREA WOULD BE FLOOD PROOFED. |
| | |
| | 4) SHEET LS-000 INDICATES THIS BUILDING TO BE AN "A" |
| | ASSEMBLY OCCUPANCY WITHOUT PROVIDING A SUB GROUP A-1- |
| | A-5. THIS BUILDING BEING FPLCOMMAND CENTER IS TRUELY A |
| | BUSINESS OCCUPANCY, FBC-B 304.1 BUSINESS GROUP B. |
| | BUSINESS GROUP B OCCUPANCY INCLUDES, AMONG OTHERS, THE |
| | USE OF A BUILDING OR STRUCTURE, OR A PORTION THEREOF, |
| | FOR OFFICE, PROFESSIONAL OR SERVICE-TYPE TRANSACTIONS, |
| | INCLUDING STORAGE OF RECORDS AND ACCOUNTS. |
| | |
| | 5) ADDITIONAL INFORMATION REQUIRED 106.1.2, DISCREPANCY |
| | IN THE PLANS. LS-201 EXIT DOORSINDICATE A 33 INCH WIDE |
| | DOOR, NOT CLEAR SPACE, THEN NEXT TO THIS STATEMENT THE |
| | GRAPHICS INDICATE A 34 INCH WIDE REQUIRED. A-201 DOORS |
| | 110 & 121 INDICATE THEY ARE |
| | 3'X7' ON THE DOOR SCHEDULE SHEET A-801. |
| | |
| | 6) A-501 & A-801 THE PLANS INDICATE WHAT PRODUCT |
| | APPROVALS WILL BE INSTALLED ON THE JOBSITE BUT THE |
| | WHOLE APPROVAL HA NOT BEEN PROVIDED. BEFORE PERMIT |
| | ISSUANCE THEY WILL NEED TO BE PROVIDED FOR REVIEW. |
| | PLEASE NOTE ON MANY WINDOW AND DOOR APPROVALS THERE ARE |
| | MORE THAN ONE TYPE GLAZING SYSTEM THAT IS PART OF THE |
| | APPROVAL. PLEASE CIRCLE WHICH GLAZED SYSTEM WILL BE |
| | INSTALLED SINCE EFFECTS THE ASSOCIATED PRESSURES. RULE |
| | 9N-3 (FORMERELY RULE 9B-72). |
| | |
| | FL BLD CODE 1609.6.2.2 COMPONENTS & CLADDING, PROVIDE 2 |
| | COPIES OF PRODUCT TESTING REPORTS, MISSING REPORTS ARE |
| | AS FOLLOWS: |
| | 6A) IMPACT WINDOWS- STOREFRONT |
| | 6B) IMPACT WINDOWS- SPANDREL (SHEET A-501) |
| | 6C) GLAZED EXTERIOR DOORS |
| | 6D) METAL EXTERIOR DOORS |
| | 6E) EXTERIOR LOUVERS |
| | 6F) ROOFING ASSEMBLIES- NO APPROVAL INFORMATION WAS |
| | SUBMITTED. PLEASE NOTE THERE MAY BE SEPERATE SUBSYSTEMS |
| | LISTED WITHIN THE PRODUCT APPROVAL REPORT, HIGHLIGHT |
| | THE INTENDED SUB-SYSTEM AND NOTE THE ASSOCIATED |
| | PRESSURES AND IF ENHANCED FASTENING IS LISTED OR IS |
| | THERE A SYSTEM LIMITATION ON THAT SUB-SYSTEM. |
| | |
| | 7) SHEET F-1 THE WIND DESIGN IS FIGURED AT 191 MPH |
| | WHICH IS HIGH, BUT THE BUILDING CATEGORY IS NOT A I BUT |
| | A LV. POWER GENERATING STATIONS AND OTHER PUBLIC |
| | UTILITIES FACILITIES REQUIRED IN AN EMERGENCY. THE |
| | IMPORTANCE FACTOR WILL CHANGE FROM A 1.0 TO A 1.15. |
| | THIS WILL CHANGE THE PRESSURES INDICATED ON THE PLANS |
| | AND POSSIBLY THE PROPOSED PRODUCT APPROVALS.. |
| | |
| | 8) SHEET F2 FLOOR SLABS PLEASE PROVIDE COMPLIANCE WITH |
| | 1816.1 TERMITE PROTECTION / 1910.1. NOTED THIS CODE |
| | SECTION DEALS WITH |
| | SLABS ON GROUND, THE FOAM MAY ACT AS A PARTIAL BARRIER |
| | BUT THE BEAM PORTION OF THE FLOOR SLAB WILL EITHER BE |
| | IN DIRECT CONTACT WITH EARTH OR DIRECTLY ABOVE THE |
| | EARTH, ALOWING MOISTURE, CONDENSATION TO ENTER THE |
| | CONCERTE BEAM PORTION OF THE FLOOR SYSTEM AND SPAWLLING |
| | WOULD OCCUR OVER A PERIOD OF TIME. ALSO APPENDIX E302.1 |
| | RADON GASSES. |
| | |
| | 9) THE SECOND ISSUE WITH FOAM INSULATION IS SHEET A-601 |
| | & A-651: |
| | 9A) INTERIOR WALLS, PLEASE PROVIDE SURFACE- BURNING |
| | CHARACTERISTICS FOR THE FOAM USED WITHIN THE POURED |
| | WALLS. FBC-B 2603.3 |
| | 9B) THE PLANS INDICATE THE INTERIOR WALLS TO BE GWB, |
| | GYPSUM WALL BOARD BUT NO THICKNESS INDICATED, PLEASE |
| | REVIEW SECTION |
| | FBC-B 2603.4. |
| | 9C) IN DETAIL # 2 THE UPPER PORTION OF WALL HAS NO |
| | INSULATION WITH IN THE WALL DOES THIS MEET WITH THE |
| | ENERGY CALCULATIONS? |
| | 9D) IN DETAIL # 2 THE CENTRAL CORE, THE CEILING |
| | INDICATES EXPOSED TO THE ROOF DECK BELOW WHICH WOULD |
| | ALLOW FOR EXPOSED FOAM INSULATION, FBC-B 2603.4. |
| | 9E) THIS SAME CONDITION EXIST IN THE MECHANICAL/ |
| | ELECTRICAL ROOM# 114 AND THE SERVER ROOM # 115. |
| | 9F) IN MANY OF THE OTHER ROOMS THE FINISH SCHEDULE |
| | INDICATES THE USE OF DROPPED CEILINGS, PLEASE INDICATE |
| | HOW THE THERMAL BARRIER WILL BE MAINTAINED. |
| | |
| | 10) SHEET A-601/ A-651 DETAIL# 3, GUTTERS AND DOWN |
| | SPOUTS, PLEASE PROVIDE THE SCHEDULE( THICKNESS) FOR THE |
| | PVC DOWNSPOUTS PER |
| | FBC-B 1503.4.1. |
| | |
| | 11) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED, IMPACT |
| | FEES MUST BE PAID TO PALM BEACH COUNTY. THE ACTUAL |
| | PERMIT SET OF PLANS MUST BE STAMPED BY THAT OFFICE, AND |
| | A COPY OF THE PAID RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION. PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | JAMES A. WITMER C.B.O. |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: (561)805-6715 |
| | FAX:(561)805-6731 |
| | E-MAIL: [email protected] |
| | |
| | CONSTRUCTION SERVICES HOME PAGE |
| | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
| | |
| | PLEASE NOTE: FLORIDA HAS A VERY BROAD PUBLIC RECORDS |
| | LAW. WRITTEN COMMUNICATIONS TO OR FROM LOCAL OFFICIALS |