| 2011-02-10 09:35:25 | 4700 NORTH CONGRESS AVENUE, SUITES 103 AND 105 | | | PERMIT #10120323 | | | REVIEW COMMENTS - FIRE | | | 2ND REVIEW | | | | | | | | | FOR ISSUANCE OF A GENERAL BUILDING PERMIT, SECTION 106 | | | AND 105.3.1.2(2) OF THE FLORIDA BUILDING CODE REQUIRES | | | FIRE PROTECTION CONSTRUCTION DOCUMENTS FOR THE DESIGN | | | OR ALTERATION OF FIRE SUPPRESSION SYSTEMS AND FIRE | | | ALARM SYSTEMS. SECTION 106.1.1.1 OF THE FBC REQUIRES | | | FIRE PROTECTION SHOP DRAWINGS TO BE SUBMITTED, UNDER A | | | SEPARATE PERMIT, AND THESE SHOP DRAWINGS SHALL BE IN | | | CONFORMANCE WITH THE CONSTRUCTION DOCUMENTS. | | | | | | A ONE-HOUR FIRE-RATED TENANT SEPARATION IS REQUIRED | | | BETWEEN INDIVIDUAL TENANT SPACES WHEN THE AREA EXCEEDS | | | 3,000 SQUARE FEET BETWEEN FIRE-RATED PARTITIONS. THE | | | DOOR AND WALL BETWEEN BUSINESS OFFICE 127 AND HALL 120 | | | ARE REQUIRED TO BE FIRE RATED. | | | | | | ELECTRICAL SHEET E-2 ONLY SHOWS TWO EXIT SIGNS IN SUITE | | | 103. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW |
|