| Plan Review Notes For Permit 10120323 |
| Permit Number |
10120323 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2011-01-03 09:43:19 | PLAN DENIED | | | OFFICE 127 HAS NO RETURN AIR ON THE PLANS. PLEASE | | | PROVIDE RETURN PER SECTION 601.4 2007 FBC (M) BALANCED | | | RETURN AIR. | | | REFER TO SECTION 601.4 2007 FBC(M) FOR EXAM ROOMS 110 | | | THROUGH 116 AND 116 . | | | PLEASE PROVIDE THE SIZE AND SPACING OF THE WEDGE | | | ANCHORS ON THE DETAIL FOR CURB TO ROOF TIE DOWN. | | | PLAN REVIEW BY HAROLD MOSER 561-805-6732 | | | |
|