| Plan Review Notes For Permit 10120323 |
| Permit Number |
10120323 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2010-12-27 16:33:35 | 4700 NORTH CONGRESS AVENUE, SUITES 103 AND 105 | | | PERMIT #10120323 | | | REVIEW COMMENTS - FIRE | | | | | | | | | INDICATE WHAT TYPE OF OCCUPANCY EXISTS EAST AND WEST OF | | | SUITE 105. | | | | | | PROVIDE PERTINENT LIFE SAFETY INFORMATION (EXIT SIGNS, | | | FIRE EXTINGUISHER LOCATIONS ETC.) ON PLAN. | | | | | | FOR A BUILDING PERMIT, FIRE PROTECTION CONSTRUCTION | | | DOCUMENTS ARE REQUIRED SHOWING/DESCRIBING THE SCOPE OF | | | THE FIRE ALARM AND FIRE SPRINKLER WORK. | | | | | | SEPARATE PLANS (SHOP DRAWINGS) AND PERMITS REQUIRED FOR | | | FIRE SPRINKLER AND FIRE ALARM | | | INSTALLATION/MODIFICATION. | | | | | | A ONE-HOUR FIRE-RATED TENANT SEPARATION IS REQUIRED | | | BETWEEN INDIVIDUAL TENANT SPACES WHEN THE AREA EXCEEDS | | | 3,000 SQUARE FEET BETWEEN FIRE-RATED PARTITIONS. | | | | | | DOES THE LARGE EXISTING ELECTRICAL ROOM HAVE A | | | FIRE-RATING? | | | | | | DOOR RELEASING MECHANISMS SHALL OPEN THE DOOR WITH NOT | | | MORE THAN ONE OPERATION. PROVIDE NEW/EXISTING DOOR | | | HARDWARE, LOCKS, AND FIRE-RATING INFORMATION. | | | | | | WESLEY JOLIN | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | |
|